GC9C80 Service Manual

SERVICING
35

Delayed ignition is a delay in lighting a combustible mixture
of gas and air which has accumulated in the combustion
chamber.
Furnace design makes this extremely unlikely unless safety
controls have been by-passed or tampered with. Never by-
pass or alter furnace controls.
If delayed ignition should occur, the following should be
checked:
1. Improper gas pressure - adjust to proper pressure.
2. Improper burner positioning - burners should be in locating
slots, level front to rear and left to right.
3. Carry over (lighter tube or cross lighter) obstructed - clean.
4. Main burner orice(s) deformed, or out of alignment to
burner - replace.


Failure to earth ground the furnace, reversing the
neutral and hot wire connection to the line (polarity), or a
high resistance connection in the neutral line may cause the
control to lockout due to failure to sense ame.
T
 T R  TR  RG T T T
T B RR R  GR
T R
BR RRG R T B

The ground wire must run from the furnace all the way back
to the electrical panel. Proper grounding can be conrmed by
disconnecting the electrical power and measuring resistance
between the neutral (white) connection and the burner closest
to the ame sensor. Resistance should be less than 2 ohms.
The ignition control is a combination electronic and
electromechanical device and is not eld repairable. Complete
unit must be replaced.
 TG  RT


A ame sensing device is used in conjunction with the ignition
control module to prove combustion. If proof of ame is not
present the control will de-energize the gas valve and “retry”
for ignition or lockout.

G
TG
T

R BR RG R
TG T
T
T R
R 
B RT
R T     RRT

G R JR
R T
Flame current can be measured by putting a D.C. microamp
meter in series with the ame rod.
 TG  RT

3. As soon as ame is established a micro-amp reading
should be evident once proof of ame (micro-amp reading)
is established, the hot surface ignitor will be de-energized.
4. The Integrated Ignition controls will have 1 to 4 micro-
amps. If the micro-amp reading is less than the minimum
specied, check for high resistance wiring connections,
sensor to burner gap, dirty flame sensor, or poor
grounding.
5. If absolutely no reading, check for continuity on all
components and if good - replace ignition control module.
Contaminated fuel or combustion air can create a
nearly invisible coating on the ame sensor. This coating
works as an insulator causing a loss in the ame sense signal.
If this situation occurs the ame sensor must be cleaned with
steel wool.

G
TG
T

R BR RG R
TG T T
T R R 
B RT
R T     RRT
G R JR R T
 T T TTR  T R
T
G
T GTR B T BR GR RG G R
BRT  RT  R GTR R

 RR  R T GTR
