GC9C80 Installation Manual

22

Refer to your furnace rating plate for the maximum ESP (ex-
ternal duct static) rating.




Total external static refers to everything external to the fur-
       
must all be considered when reading your total external
static pressure. The supply duct pressure must be read be-
tween the furnace and the cooling coil.
This reading is usually taken by removing the “A” shaped
󰀨 
    󰀨  
reading at the test hole. Tape up the test hole after your test
is complete. The negative pressure must be read between

󰀩
that can cause excessive temperature rise. This can cause
limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as
follows:
1.   
measure the static pressure of the return duct at the
inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct. (Positive
Pressure)
3. 󰀨




Both readings may be taken simultaneously and read
directly on the manometer if so desired. If an air conditioner

furnace, the readings must also include theses components,
as shown in the following drawing.
4. 
If the total external static pressure exceeds the maximum list-
ed on the furnace rating plate, check for closed dampers, reg-
isters, undersized and/or oversized poorly laid out duct work.
The temperature rise of the furnace must be within the tem-
perature rise range listed on the furnace rating plate.



1.     󰀨    
furnace.
2. 󰀨
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
 This furnace is equipped with an ignition device

burner by hand.
5. Move the furnace gas valve manual con
position.
6. 

7. 
the safety instructions in the Safety Considerations on

minutes, move the furnace gas valve manual control to
the ON position.
8. Replace the burner compartment door.
9.     󰀨    
furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room
temperature.
12. After the burners are lit, set the thermostat to desired
temperature.