Daikin EHK Specification Sheet
6 www.daikincomfort.com SS-DEHK
SS-DEHK www.daikincomfort.com 7
Product SPecificationS
Product SPecificationS
electric Heat Kits for Dcc/DcH PacKageD uNits — 15 & 20 toNs
Dcc 15-toN uNits — Heat Kit usage Dcc 20-toN uNits — Heat Kit usage
Three-Phase Units @ 208 / 240V Three-Phase Units @ 208 / 240V
Model MCA¹
MOP²
(amps)
kW &
BTU/h
Recommended
Airflow Range
Model MCA¹
MOP²
(amps)
kW &
BTU/h
Recommended
Airflow Range
DCC181***3B*** 73 90 DCC240***3B*** 95 125
EHK3-31 98 100 28.8 5250 - 6750 CFM EHK3-31 103 125 28.8 7200 - 8500 CFM
EHK3-46 141 150 43.2 5250 - 6750 CFM EHK3-46 146 150 43.2 7200 - 8500 CFM
EHK3-60 185 200 57.6 5250 - 6750 CFM
EHK3-60 189 200 57.6 7200 - 8500 CFM
EHK3-75 232 250 72 7200 - 8500 CFM
480-Volt Units @ 480V 480-Volt Units @ 480V
Model MCA¹
MOP²
(amps)
kW &
BTU/h
Recommended
Airflow Range
Model MCA¹
MOP²
(amps)
kW &
BTU/h
Recommended
Airflow Range
DCC181***4B*** 36 45 DCC240***4B*** 50 60
EHK4-31 49 50 28.8 5250 - 6750 CFM EHK4-31 51 60 28.8 7200 - 8500 CFM
EHK4-46 71 80 43.2 5250 - 6750 CFM EHK4-46 73 80 43.2 7200 - 8500 CFM
EHK4-60 92 100 57.6 5250 - 6750 CFM
EHK4-60 95 100 57.6 7200 - 8500 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon (amps)
EHK4-75 116 125 72 7200 - 8500 CFM
575-Volt Units @ 575V 575-Volt Units @ 575V
Model MCA¹
MOP²
(amps)
kW &
BTU/h
Recommended
Airflow Range
Model MCA¹
MOP²
(amps)
kW &
BTU/h
Recommended
Airflow Range
DCC181***7B*** 27 35 DCC240***7B*** 37 45
EHK7-31 41 45 28.8 5250 - 6750 CFM EHK7-31 43 45 28.8 7200 - 8500 CFM
EHK7-46 59 60 43.2 5250 - 6750 CFM EHK7-46 61 70 43.2 7200 - 8500 CFM
EHK7-60 78 80 57.6 5250 - 6750 CFM
EHK7-60 79 80 57.6 7200 - 8500 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon (amps)
EHK7-75 97 100 72 7200 - 8500 CFM