Daikin EHK Specification Sheet

6 www.daikincomfort.com SS-DEHK
SS-DEHK www.daikincomfort.com 7
Product SPecificationS
Product SPecificationS
Dcc 7½- to 12½-toN uNits Heat Kit usage DcH 7½- to 12½-toN uNits Heat Kit usage
575-Volt Units @ 575V 575-Volt Units @ 575V
Model MCA¹
MOP²
(amps)
kW &
BTU/h
Recommended
Airflow Range
Model MCA¹
MOP²
(amps)
kW &
BTU/h
Recommended
Airflow Range
DCC090***7B*** 14 15 DCH090***7B*** 14 15
EHK7-16 22 25 15 --- EHK7-16 33 35 15 ---
EHK7-30 41 45 30 --- EHK7-30 51 60 30 ---
EHK7-45 57 60 43 --- EHK7-45 68 70 43 ---
DCC102***7B*** 17 20 DCH102***7B*** 17 20
EHK7-16 22 25 15 3400 - 3825 CFM EHK7-16 36 40 15 3400 - 3825 CFM
EHK7-30 41 45 30 3400 - 3825 CFM EHK7-30 55 60 30 3400 - 3825 CFM
EHK7-45 57 60 43 3400 - 3825 CFM EHK7-45 71 80 43 3400 - 3825 CFM
DCC120***7B/V*** 17 20 DCH120***7B/V*** 17 20
EHK7-16 22 25 15 3,500-4,500 CFM EHK7-16 36 40 15 3,500-4,500 CFM
EHK7-30 41 45 30 3,500-4,500 CFM EHK7-30 55 60 30 3,500-4,500 CFM
EHK7-45 57 60 43 4,000-4,500 CFM EHK7-45 71 80 43 4,000-4,500 CFM
DCC150***7B*** 23 30 DCH150***7B*** 23 30
EHK7-16 24 30 15 4,000-5,600 CFM EHK7-16 42 45 15 4,000-5,600 CFM
EHK7-30 43 45 30 4,300-5,600 CFM EHK7-30 61 70 30 4,300-5,600 CFM
EHK7-45 59 60 43 4,500-5,600 CFM EHK7-45 77 80 43 4,500-5,600 CFM
¹ Minimum Circuit Ampacity ¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon device ² Maximum Overcurrent Protecon device
electric Heat Kits for Dcc/DcH PacKageD uNits 7½ to 12½ toNs
kW Correction Factor for 3-phase Units
Supply Voltage 240 230 220 210
Correction Factor 1 0.92 0.84 0.77
kW Correction Factor for 480V Units
Actual Voltage 460 440 430
Correction Factor 0.92 0.84 0.8
For other voltage use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage 560 550 540
Correction Factor 0.95 0.91 0.88
Mulply rated kW by correcon factor to get actual kW.
KW correctioN factors