AVPTC Service Manual
21
ACCESSORIES
ELECTRIC HEAT KIT APPLICATIONS - AVPTC
* Revision level that may or may not be designated.
C Circuit breaker option.
NOTE:
When 8kW and 10kW heat kits are used with an AVPTC1830 and AVPTC3137, matched with 2- ton outdoor unit, see Note 1 below.
1
Set Heater Kit dip switches 9, 10 and 11 to 6kW setting (9-ON, 10-OFF,11-ON) to obtain 840 CFM.
2
This heater kit can only be used for ‘1000 CFM or higher’ applications.
3
This heater kit can only be used for ‘1200 CFM or higher’ applications.
MODELS HKR-03* HKR-05*/-05C* HKR-06* HKR-08*/-08C* HKR-10*/-10C* HKR-15C* HKR-20C* HKR-21C* HKA-15C* HKA-20C*
AVPTC183014A* X X X
X
1
X
1
--- --- --- --- ---
AVPTC313714A* X X X
X
1
X
1
X2 --- ---
X
2
X
AVPTC426014A* X X X X X X X3 X3 X
X
3