AVPTC Service Manual

SERVICING
48
Symptoms of Abnormal Operation
(Legacy & ComfortNet Thermostat)
Dia gnostic/ Status LED Codes
Fault
Description
Comf or t N e t
Thermostat Only
Possible Causes
Corrective Actions Notes & Cautions
Green Ye l l o w Red Red Y1 Message Code
Very long run time.
Four consecutive compressor protector
trips with average run time between
trips greater than 3 hours.
Compressor operating at high speed
and outdoor fan operating at low speed
Integrated control module
diagnost ic/status LEDs display the
indicated code.
OFF 1 Flash OFF ON if call
present;
OFF if no
call
Low Side Fault. LOW SIDE
FAULT
01 Low refrigerant charge.
Restriction in liquid line.
Indoor blower motor
failure.
Indoor thermostat set
extremely low.
Verify re fri gerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Fault will clear after 30
consecutive normal
cycles.
Fault may be cleared by
cycling 24VAC to
control.
Replace with correct
replacement part(s).
Compressor a nd out door fan are off.
Thermostat demand is present.
Integrated control module
diagnost ic/status LEDs display the
indicated code.
ON 1 Flash OFF ON if call
present;
OFF if no
call
Low Pressure
CO Trip.
LPS OPEN 01
Low refrigerant charge.
Restriction in liquid line.
Indoor blower motor
failure.
Indoor thermostat set
extremely low.
Verify re fri gerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check low pressure
switch; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Replace with correct
replacement part(s).
Compressor a nd out door fan are off.
Low pressure switch trip 3 times within
same thermostat demand.
Thermostat demand is present.
Integrated control module
diagnost ic/status LEDs display the
indicated code.
ComfortNet™ thermostat “Call for
Service” icon illuminated.
ComfortNet™ thermostat scrolls
Check Air Conditioner orCheck
Heat Pump” message.
ON 1 Flash ON ON if call
present;
OFF if no
call
LPCO Lockout
(3 Trips).
LPS
LOCKOUT
01
Low refrigerant charge.
Restriction in liquid line.
Indoor blower motor
failure.
Indoor thermostat set
extremely low.
Verify re fri gerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check low pressure
switch; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Must clear fault by
cycling 24VAC to
control.
Replace with correct
replacement part(s).
PCBHR101-103
PBBGR101-102