AVPTC Service Manual

ACCESSORIES
22
†For match up with a 2 ton outdoor unit: Hea ter ki t appl i caƟon shall not exceed 10 kW.
Ai rfl ow for 5 kW u
p
to 10 kW heater kits shall be set to 850 cfm s
p
eed ta
p
of ON-ON-ON.
††For match u
p
wi th a 3 ton outdoor uni t: He ater ki t a
pp
licaƟon shall not exceed 15 kW.
Airflow for 5 kW u
p
to 15 kW he ater ki ts sha ll be s et to 1400 cfm s
p
eed ta
p
of ON-ON-OFF.
†††For match u
p
wi th a 3.5 ton outdoor uni t: He ate r ki t a
pp
licaƟon shall not exceed 20 kW.
Airflow for 5 kW u
p
to 20 kW hea ter ki ts s hall be set to 1620 cfm s
p
eed ta
p
of ON-ON-OFF
** 3 kW heater kit is not applicable for this indoor application.
AVPTC**14**
Heat Kit Applications
Type / Model 24B14-A* 30C14-A* 36C14-A* 48C14-A* 42D14-A*
48D14-A*
††
60D14-A*
†††
HKSX03XC X X X
HKSX05XC XXXXXXX
HKSX06XC XXXXXXX
HKSX08XC XXXXXXX
HKSX10XC XXXXXXX
HKSX15XF* XXXXX
HKSX20XF* XXXXX
HKSC05XC XXXXXXX
HKSC08XC XXXXXXX
HKSC10XC XXXXXXX
HKSC15XA XXXXX
HKSC15XB XXXXX
HKSC15XF* XXXXX
HKSC19CA* X X
HKSC19CB* X X
HKSC20DA XXX
HKSC20DB XXX
HKSCX20XF* XXXXX
HKSC25DC* XX
* Revision level that may or may not be designated.
Refer to the minimum airflow requirements for each of the heat kits.
AVPTC