Updated Dipswitch Settings
MEMORY CHIPS FOR
COMMUNICATING AIR HANDLERS
IO-MC5
04/2014
New Airflow and Dipswitch Settings for AVPTC and DV**PTC Air Handlers
Htr kw S9 S10 S11 24B 30C 36C 48C† 42D† 48D†† 60D†††
3 on on on 550 600 NR NR 850** NR NR
5 on on off 650 700 850 850 1250 1250 1250
6 on off on 700 750 900 900 1300 1300 1300
8 on off off 800 875 1000 1000 1500 1500 1500
10 off on on 850 950 1200 1200 1550 1550 1550
15 off on off NR NR 1440 1440 1720 1720 1780
19 off off on NR NR 1500 1500 NR NR NR
20 off off on NR NR 1500 1500 1800 1815 1850
21 or 25 off off off NR NR NR NR NR 1850 1850
New AVPTC & DV**PTC Airflow S
p
ecification for Heater Kits
Notes:
†For match up with a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW.
Airflow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of ON-ON-ON.
††For match up with a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW.
Airflow for 5 kW up to 15 kW heater kits shall be set to
1300
cfm speed tap of
ON-OFF-ON.
†††For match up with a 3.5 ton outdoor unit: Heater kit application shall not exceed 20 kW.
Airflow for 5 kW up to 20 kW heater kits shall be set to
1500
cfm speed tap of
ON -OFF-OFF.
** 3 kW heater kit is not applicable for this indoor application.