AVPTC Series Specification Sheet
8 www.goodmanmfg.com SS-GAVPTC
SS-GAVPTC www.goodmanmfg.com 9
Airflow Data (cont.)
Model Speed Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
AVPTC59D14AA
A Low 1030 1035 1040 1040 1030 1025 1015 995 970
B Low 1260 1260 1260 1260 1260 1250 1245 1235 1225
C Low 1330 1335 1330 1330 1325 1320 1315 1305 1295
D Low 1395 1395 1395 1390 1390 1385 1375 1365 1355
A High 1450 1445 1445 1435 1430 1425 1420 1410 1395
B High 1795 1790 1790 1785 1775 1765 1760 1750 1745
C High 1890 1890 1890 1880 1870 1865 1855 1850 1840
D High 1995 1995 1990 1985 1985 1975 1965 1955 1945
AVPTC60D14
A Low 1205 1205 1210 1205 1205 1200 1195 1195 1195
B Low 1375 1370 1365 1360 1360 1355 1355 1350 1350
C Low 1445 1445 1450 1445 1445 1440 1440 1440 1435
D Low 1535 1530 1525 1520 1520 1515 1510 1510 1510
A High 1615 1615 1610 1610 1605 1605 1600 1600 1600
B High 1825 1820 1815 1810 1810 1805 1805 1805 1800
C High 1930 1925 1920 1915 1915 1910 1905 1905 1900
D High 2040 2030 2025 2020 2015 2010 2005 2005 2000
AVPTC61D14AA
A Low 1080 1085 1080 1085 1080 1075 1070 1065 1055
B Low 1200 1200 1210 1210 1210 1210 1205 1205 1200
C Low 1290 1290 1280 1275 1280 1280 1270 1265 1265
D Low 1360 1355 1350 1355 1350 1345 1340 1340 1330
A High 1630 1630 1630 1625 1620 1615 1610 1600 1590
B High 1820 1820 1820 1815 1805 1795 1785 1780 1770
C High 1935 1930 1925 1920 1905 1900 1890 1875 1865
D High 2035 2030 2025 2020 2005 1995 1985 1960 1955
Note: When applying a humidistat (normally closed), refer to the installaon and operang instrucons. The humidistat can adjust the cooling airow to 85%.