AVPTC Installation Instructions ComfortBridge
13
FIgure 17
Figure 18
Figure 19
2. Download the Cool Cloud HVAC phone applicaon.
Note: When new versions of Bluetooth Communicaon
Soware and Air Handler Control Soware are available,
the phone applicaon noes the user. Soware updates
are classied as either oponal or mandatory and installed
by using the phone applicaon. Ensure all mandatory
soware updates have been installed. Review notes for
oponal soware updates and install if necessary.
3. Go to the Non-Comm Outdoor Seng Menu () using
the on board push buons or the Cool Cloud HVAC phone
applicaon. Selec t “” for single stage Air Condioners,
“” for single stage Heat Pumps, “” for two stage Air
Condioners and “” for 2 stage Heat Pumps.
4. Go to the Tonnage Units Menu () and select the ton-
nage value that corresponds to the desired airow for the
outdoor unit. See the following table.
NOTE: For the two stage non-communicang outdoor
units, system will stage airow automacally for low stage
operaon.
Tonnage
Selecon
Airow
Tonnage
Selecon
Airow
Tonnage
Selecon
Airow
Tonnage
Selecon
Airow
1 400 2.3 920 3.6 1440 4.9 1960
1.1 440 2.4 960 3.7 1480 5 2000
1.2 480 2.5 1000 3.8 1520 5.1 2040
1.3 520 2.6 1040 3.9 1560 5.2 2080
1.4 560 2.7 1080 4 1600 5.3 2120
1.5 600 2.8 1120 4.1 1640 5.4 2160
1.6 640 2.9 1160 4.2 1680 5.5 2200
1.7 680 3 1200 4.3 1720 5.6 2240
1.8 720 3.1 1240 4.4 1760 5.7 2280
1.9 760 3.2 1280 4.5 1800 5.8 2320
2 800 3.3 1320 4.6 1840 5.9 2360
2.1 840 3.4 1360 4.7 1880 6 2400
2.2 880 3.5 1440 4.8 1920
NOTE: The system will not provide airows above the max Airow
Value.