Specifications
6 www.goodmanmfg.com SS-GAVPTC
SS-GAVPTC www.goodmanmfg.com 7
Airflow Data (cont.)
Model
Speed Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
AVPTC35B14
A Low 395 390 395 390 385 380 380 380 380
B Low 580 580 590 580 575 580 575 575 575
C Low 670 670 680 690 680 670 660 660 665
D Low 715 705 710 720 715 705 690 685 680
A High 645 630 645 645 635 630 630 635 635
B High 900 875 870 870 870 870 865 855 845
C High 1030 1015 1005 995 990 985 990 990 980
D High 1075 1060 1045 1035 1030 1025 1020 1020 1015
AVPTC37D14AC
A Low 605 605 605 575 560 545 525 510 500
B Low 730 725 725 700 700 695 680 660 645
C Low 820 820 820 800 760 750 740 720 700
D Low 870 885 940 885 875 865 850 835 835
A High 910 905 900 870 870 860 855 845 845
B High 1085 1080 1080 1060 1060 1055 1045 1035 1020
C High 1230 1225 1225 1205 1205 1200 1190 1185 1180
D High 1405 1405 1405 1370 1365 1355 1345 1335 1330
AVPTC39C14AC
A Low 715 695 680 685 685 680 675 665 650
B Low 755 770 780 780 780 780 770 765 755
C Low 780 790 795 805 800 800 795 805 795
D Low 875 885 890 890 890 890 885 880 875
A High 960 960 965 970 965 965 960 955 950
B High 1120 1115 1115 1115 1120 1115 1115 1110 1105
C High 1180 1180 1175 1175 1175 1175 1170 1165 1160
D High 1325 1320 1315 1315 1310 1310 1310 1305 1300
AVPTC42D14
A Low 600 580 560 545 535 520 505 500 490
B Low 795 780 765 750 740 730 720 715 710
C Low 1025 1010 995 985 970 960 950 945 940
D Low 1250 1235 1225 1215 1210 1200 1195 1190 1185
A High 835 815 800 790 780 765 755 750 745
B High 1115 1105 1090 1080 1070 1065 1055 1050 1045
C High 1445 1430 1420 1410 1405 1395 1390 1385 1380
D High 1775 1760 1750 1740 1735 1725 1720 1715 1710
AVPTC48C14
A Low 510 505 500 490 485 480 475 465 455
B Low 710 705 700 690 680 680 670 660 650
C Low 940 935 930 920 910 910 905 890 880
D Low 1165 1160 1160 1155 1150 1145 1140 1135 1125
A High 735 730 725 715 705 700 695 685 675
B High 1010 1005 1000 990 985 980 975 965 955
C High 1340 1335 1330 1320 1310 1310 1305 1290 1280
D High 1675 1665 1660 1645 1635 1630 1620 1605 1590
Note:Whenapplyingahumidistat(normallyclosed),refertotheinstallaonandoperanginstrucons.Thehumidistatcanadjustthecoolingairowto85%.