Specifications

6 www.goodmanmfg.com SS-GAVPTC
SS-GAVPTC www.goodmanmfg.com 7
Airflow Data
Model
Speed Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
AVPTC24B14
A Low 415 415 410 410 405 405 400 400 400
B Low 575 570 565 560 560 555 555 550 550
C Low 685 670 660 650 645 635 630 625 620
D Low 795 780 765 755 745 735 725 720 715
A High 620 615 610 605 600 600 595 590 590
B High 865 850 835 825 815 805 795 790 785
C High 1005 990 970 960 945 935 920 915 910
D High 1165 1145 1125 1110 1100 1085 1070 1065 1055
AVPTC25B14AB
A Low 460 445 445 425 410 400 400 400 395
B Low 620 610 600 605 600 590 585 575 565
C Low 700 695 690 690 690 690 675 665 660
D Low 750 750 745 745 740 730 720 710 700
A High 670 660 650 650 655 645 640 635 625
B High 870 865 855 850 840 840 840 830 835
C High 1000 990 980 975 965 965 955 955 945
D High 1105 1095 1085 1075 1065 1055 1050 1040 1030
AVPTC29B14AB
AVPTC37B14AB
A Low 390 385 375 360 350 335 325 315 305
B Low 545 540 545 540 540 540 535 530 525
C Low 610 620 630 635 630 625 620 625 625
D Low 720 735 740 740 735 730 725 715 705
A High 615 620 610 605 610 615 615 620 625
B High 790 795 795 795 795 790 800 795 785
C High 925 930 930 925 925 920 915 910 905
D High 1085 1085 1085 1080 1080 1075 1070 1065 1060
AVPTC31C14AD
AVPTC37C14AC
A Low 610 600 590 590 600 605 610 610 610
B Low 710 710 705 705 695 690 685 675 665
C Low 845 845 845 825 815 810 800 805 795
D Low 915 910 910 900 850 840 830 820 825
A High 885 880 880 860 850 840 830 820 830
B High 1055 1055 1055 1040 1030 1015 1005 995 985
C High 1275 1270 1265 1260 1250 1240 1230 1215 1205
D High 1365 1360 1360 1330 1300 1290 1280 1270 1255
AVPTC33C14AB
A Low 500 480 460 445 430 415 400 380 365
B Low 580 565 545 535 525 515 505 495 485
C Low 710 700 685 675 670 665 655 645 640
D Low 725 750 755 760 755 745 735 725 715
A High 710 700 685 685 685 680 670 660 645
B High 765 780 785 785 785 775 770 760 745
C High 950 960 970 970 970 960 955 945 935
D High 1090 1090 1090 1095 1090 1085 1080 1075 1065
Note:Whenapplyingahumidistat(normallyclosed),refertotheinstallaonandoperanginstrucons.Thehumidistatcanadjustthecoolingairowto85%.