ASPT Service Manual

Table Of Contents
SERVICING
93
4. If the pressure rises to 1000 microns or less and remains
steady the system is considered leak free; proceed to
startup.
5. If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or non-condensibles
may be present or the system may have a small leak.
6. Return to step 2: If the same result is encountered check for
leaks as previously indicated and repair as necessary
then repeat evacuation.
7. If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as
necessary then repeat evacuation.
LOW SIDE
GAUGE
AND VALVE
HIGH SIDE
GAUGE
AND VALVE
TO
UNIT SERVICE
VALVE PORTS
VACUUM PUMP
VACUUM PUMP
ADAPTER
800 PSI
RATED
HOSES
CHARGING
CYLINDER
AND SCALE
Charging
WARNING






CAUTION





CAUTION




Charge the system with the exact amount of refrigerant.
Refer to the specication section or check the unit
nameplates for the correct refrigerant charge. An
inaccurately charged system will cause future problems.

container or drum in liquid form due to its fractionation



charging hose set to accomplish this. DO NOT charge
liquid R410A into the compressor.


applied to the indoor unit. Sending a low voltage signal
without high voltage power present at the outdoor unit
can cause malfunction of the control module on the
ECM motor.
Adequate refrigerant charge for the matching evaporator
coil or air handler and 15 feet of line set is supplied with the
condensing unit. If using evaporator coils or air handlers
other than HSVTC coil it may be necessary to add or
remove refrigerant to attain proper charge. If line set
exceeds 15 feet in length, refrigerant should be added at .6
ounces per foot of liquid line.

higher when charging the unit.Charge should always

equipped indoor coil to verify proper charge. Open the



󰀨
When opening valves with retainers, open each valve
only until the top of the stem is 1/8” from the retainer. To
avoid loss of refrigerant, DO NOT apply pressure to the
retainer. When opening valves without a retainer remove
service valve cap and insert a hex wrench into the valve
stem and back out the stem by turning the hex wrench
counterclockwise. Open the valve until it contacts the rolled
lip of the valve body.

necessary to force the stem tightly against the rolled
lip.