ASPT Service Manual

Table Of Contents
SERVICING
88
WARNING

If the compressor starts and continues to run, the cause
for failure is somewhere else in the system.
If the compressor fails to start - replace.
COPELAND COMPRESSOR
03 A 12345 L
YEAR
MONTH
SERIAL
NUMBER
PLANT

Verify the proper rotation of Copeland scroll compressors
as follows:


normal and does not harm the compressor.
1. Install gauges and verify that the suction pressure drops
while the discharge pressure increases.
2. Listen for normal compressor sound levels. Reverse
rotation results in elevated or unusual sound levels.
3. Reverse rotation will result in substantially reduced amp
draw from tabulated values.
To correct improper rotation, switch any two power supply
leads at the outdoor unit contactor.
The 3-phase scroll compressors are direction of rotation
sensitive. They will rotate in either direction depending on
the phasing of the power. There is no negative impact on
durability caused by operating 3-phase compressors in
reversed rotation. The compressor’s internal protector will
trip, de-energizing the compressor. Continued operation
of 3-phase scroll compressors with the rotation reversed
will contribute to compressor failure. All 3-phase scroll
compressors should be checked for correct phase rotation.

The crankcase heater must be energized a minimum of
four (4) hours before the condensing unit is operated.
Crankcase heaters are used to prevent migration or
accumulation of refrigerant in the compressor crankcase
during the o󰀨 cycles and prevents liquid slugging or oil
pumping on start up.
A crankcase heater will not prevent compressor damage
due to a oodback or over charge condition.
WARNING

1. Disconnect the heater lead in wires.
2. Using an ohmmeter, check heater continuity - should test
continuous. If not, replace.
󰀩
heater is a 40 watt 265 voltage heater. The cool


temperature of the compressor shell increases.

Reversing valve used in heat pumps could potentially leak
internally. Discharge gases can leak into the suction inside
the valve. Compound gages will give the same symptoms
as bad compressor valves or broken scroll anks. The
temperature between true suction and the suction line after
the valve should not be greater than 4 degrees. Note: The
center tube is always the suction line and should be cold.

Failure
1. Place unit into the cooling mode. Test for 24 volts at the
solenoid. If there is no voltage present at coil, check the
control voltage.
2. If voltage is present, loosen the nut on the top of the coil.
Remove the coil, there should be slight resistance.
3. If the slight resistance is felt, remove the coil. As you
remove the coil listen carefully, an audible click should be
detected. The clicking is due to the movement of the pilot
valve plunger. The absence of a clicking sound indicates
the plunger is stuck.


1. Troubleshooting the reversing valve can be done by
pressure and touch.
2. Raise the head pressure. In the cooling mode block the
fan exhaust. Once head pressure has been raised, cycle
between cooling and heating and see if the piston can
be freed.