ASPT Service Manual
Table Of Contents
- IMPORTANT INFORMATION
- PRODUCT IDENTIFICATION
- Checking Voltage
- Checking Wiring
- Checking Thermostat And Wiring
- Thermostat Wiring
- Checking Transformer And Control Circuit
- Checking Contactor And/Or Relays
- Checking Contactor Contacts
- Checking Fan Relay Contacts
- Checking Loss Of Charge Protector (Heat Pump Models)
- Checking High Pressure Control
- Checking Low Pressure Control
- Copeland Comfort Alert™ Diagnostics - 3-Wire module
- Copeland Coresense™ Diagnostics - 3-Wire module
- Checking Capacitor
- Resistance Check Using A Digital Multi-Meter
- Capacitance Check Using A Digital Multi-Meter (In Capacitance Mode)
- Testing a Run Capacitor Under Load
- Checking Outdoor Fan and Blower Motors (PSC Motors)
- Checking Fan and Blower Motor (ECM Motors)
- Checking ECM Motor Windings
- ECM CFM Adjustments MBE/AEPF
- Blower Performance Data
- Checking High Efficiency Motors
- EEM Blower Replacement
- MBR/AR*F Electronic Blower Time Delay Relay
- Checking Compressor
- Resistance Test
- Ground Test
- Unloader Test Procedure
- Operation Test
- Checking 3-Phase Scroll Compressor Rotation
- Testing Crankcase Heater (Optional Item)
- Checking Reversing Valve and Solenoid
- Testing Defrost Control
- Testing Defrost Thermostat
- Checking Heater Limit Control(s)
- Checking Heater Elements
- Electric Heater (Optional Item)
- Checking Heater Limit Control(s)
- Checking Heater Elements
- Refrigeration Repair Practice
- Leak Testing (Nitrogen or Nitrogen-Traced)
- Evacuation
- Charging
- Checking Compressor Efficiency
- Overfeeding
- Underfeeding
- Checking Superheat
- Subcooling on Expansion Valve System
- Checking Expansion Valve Operation
- Checking Restricted Liquid Line
- Overcharge Of Refrigerant
- Non-Condensables
- Compressor Burnout
- Refrigerant Piping
- Duct Static Pressures
- Single Piece Air Handler External Static
- Two Piece Air Handler External Static Pressure
- Furnace External Static Pressure
- Periodic Maintenance
SERVICING
84
EEM Blower Replacement
For AWUF19-25, AWUF31-32, and AWUF37 Air Handlers.
1. Disconnect power at main electrical panel.
2. Remove front access panel.
3. Remove the two screws on each side holding the lower
control box and move out of the way to give access to the
blower assembly
4. Loosen or remove set screw on blower wheel hub and
ensure the wheel slides freely on the shaft of the motor.
5. Install cardboard or rug over coil to protect ns from
damage.
6. Remove the three 3/8” screws holding the blower in place.
7. Lower blower onto coil.
8. Slide blower assembly all the way to the left side of cabinet.