ASPT Service Manual
Table Of Contents
- IMPORTANT INFORMATION
- PRODUCT IDENTIFICATION
- Checking Voltage
- Checking Wiring
- Checking Thermostat And Wiring
- Thermostat Wiring
- Checking Transformer And Control Circuit
- Checking Contactor And/Or Relays
- Checking Contactor Contacts
- Checking Fan Relay Contacts
- Checking Loss Of Charge Protector (Heat Pump Models)
- Checking High Pressure Control
- Checking Low Pressure Control
- Copeland Comfort Alert™ Diagnostics - 3-Wire module
- Copeland Coresense™ Diagnostics - 3-Wire module
- Checking Capacitor
- Resistance Check Using A Digital Multi-Meter
- Capacitance Check Using A Digital Multi-Meter (In Capacitance Mode)
- Testing a Run Capacitor Under Load
- Checking Outdoor Fan and Blower Motors (PSC Motors)
- Checking Fan and Blower Motor (ECM Motors)
- Checking ECM Motor Windings
- ECM CFM Adjustments MBE/AEPF
- Blower Performance Data
- Checking High Efficiency Motors
- EEM Blower Replacement
- MBR/AR*F Electronic Blower Time Delay Relay
- Checking Compressor
- Resistance Test
- Ground Test
- Unloader Test Procedure
- Operation Test
- Checking 3-Phase Scroll Compressor Rotation
- Testing Crankcase Heater (Optional Item)
- Checking Reversing Valve and Solenoid
- Testing Defrost Control
- Testing Defrost Thermostat
- Checking Heater Limit Control(s)
- Checking Heater Elements
- Electric Heater (Optional Item)
- Checking Heater Limit Control(s)
- Checking Heater Elements
- Refrigeration Repair Practice
- Leak Testing (Nitrogen or Nitrogen-Traced)
- Evacuation
- Charging
- Checking Compressor Efficiency
- Overfeeding
- Underfeeding
- Checking Superheat
- Subcooling on Expansion Valve System
- Checking Expansion Valve Operation
- Checking Restricted Liquid Line
- Overcharge Of Refrigerant
- Non-Condensables
- Compressor Burnout
- Refrigerant Piping
- Duct Static Pressures
- Single Piece Air Handler External Static
- Two Piece Air Handler External Static Pressure
- Furnace External Static Pressure
- Periodic Maintenance
PRODUCT DESIGN
55
Molded Plug w/
Rectifier
24 Vac
Line
Line
Run Capacitor
C
R
S
Internal Unloader
Coil
FIGURE B
1. It is expected that the majority of run hours will be in the
low capacity, unloaded mode.
2. It allows a simple two-stage thermostat to control capacity
through the second stage in both cooling and possibly
heating if desired.
Unloader Solenoid
A nominal 24-volt direct current coil activates the internal
unloader solenoid. The input control circuit voltage must be
18 to 28 volt ac. The coil power requirement is 20 VA. The
external electrical connection is made with a molded plug
assembly. This plug is connected to the Comfort Alert™
or CoreSense™ Module (dependent upon which module
you are using) which contains a full wave rectier to supply
direct current to the unloader coil.