ASPT Service Manual
Table Of Contents
- IMPORTANT INFORMATION
- PRODUCT IDENTIFICATION
- Checking Voltage
- Checking Wiring
- Checking Thermostat And Wiring
- Thermostat Wiring
- Checking Transformer And Control Circuit
- Checking Contactor And/Or Relays
- Checking Contactor Contacts
- Checking Fan Relay Contacts
- Checking Loss Of Charge Protector (Heat Pump Models)
- Checking High Pressure Control
- Checking Low Pressure Control
- Copeland Comfort Alertâ„¢ Diagnostics - 3-Wire module
- Copeland Coresenseâ„¢ Diagnostics - 3-Wire module
- Checking Capacitor
- Resistance Check Using A Digital Multi-Meter
- Capacitance Check Using A Digital Multi-Meter (In Capacitance Mode)
- Testing a Run Capacitor Under Load
- Checking Outdoor Fan and Blower Motors (PSC Motors)
- Checking Fan and Blower Motor (ECM Motors)
- Checking ECM Motor Windings
- ECM CFM Adjustments MBE/AEPF
- Blower Performance Data
- Checking High Efficiency Motors
- EEM Blower Replacement
- MBR/AR*F Electronic Blower Time Delay Relay
- Checking Compressor
- Resistance Test
- Ground Test
- Unloader Test Procedure
- Operation Test
- Checking 3-Phase Scroll Compressor Rotation
- Testing Crankcase Heater (Optional Item)
- Checking Reversing Valve and Solenoid
- Testing Defrost Control
- Testing Defrost Thermostat
- Checking Heater Limit Control(s)
- Checking Heater Elements
- Electric Heater (Optional Item)
- Checking Heater Limit Control(s)
- Checking Heater Elements
- Refrigeration Repair Practice
- Leak Testing (Nitrogen or Nitrogen-Traced)
- Evacuation
- Charging
- Checking Compressor Efficiency
- Overfeeding
- Underfeeding
- Checking Superheat
- Subcooling on Expansion Valve System
- Checking Expansion Valve Operation
- Checking Restricted Liquid Line
- Overcharge Of Refrigerant
- Non-Condensables
- Compressor Burnout
- Refrigerant Piping
- Duct Static Pressures
- Single Piece Air Handler External Static
- Two Piece Air Handler External Static Pressure
- Furnace External Static Pressure
- Periodic Maintenance
WIRING DIAGRAMS
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
103
EMERGENCY
HEAT
RELAY
1 3
4 2
BLUE
WHITE
BLACK
BROWN
THERMOSTAT
OT/EHR18-60
21
From Air Handler
C G W2 R
C R W2 O Y
From Outdoor Unit
C
G
W2
E
R
O
Y
Indoor Thermostat
BLUE
GREEN
WHITE
RED
BLUE
RED
WHITE
ORANGE
YELLOW
10kw and Below, One Stage Electric Heat
RED
EMERGENCY
HEAT
RELAY
1
4 2
BLUE
WHITE
BLACK
BROWN
THERMOSTAT
OT/EHR18-60
2
1
From Air Handler
C G W2 R
C R W2 O Y
From Outdoor Unit
C
G
W2
E
R
O
Y
Indoor Thermostat
W3
BLUE
GREEN
WHITE
RED
BROWN
BLUE
RED
WHITE
ORANGE
YELLOW
15kw and Above, Two Stage Electric Heat
3
RED
SEE NOTE
Note:
When using a Thermostat with only one
stage for electric heat (W2), tie white and
brown wires from air handler together.
Typical Wiring Schematics for OT/EHR18-60 (Outdoor Thermostat & Emergency Heat Relay).
This wiring diagram is for reference only. Not all wiring is as shown above.
Refer to the appropriate wiring diagram for the unit being serviced.