Install Instructions
11
3 5 6 8 10 15 19 20 25
18 715 715 715 715 950
24 715 715 715 715 950
30B 715 715 715 715 875 875
30C 1170 1170 1170 1170 1345 1345
36 1170 1170 1170 1170 1345 1345
42 1170 1170 1170 1170 1345 1345
48 1590 1590 1590 1590 1715 1715 1715
60 1590 1590 1590 1590 1715 1715 1715
*ARUF
ARPT
HEATER (Kw )
* Table applies t o ARUF* * 14* * , ARPT* * 14* *
Table 5
3 5 6 8 10 15 19 20 25
24 715 715 715 715 875
30 715 715 715 715 950
36 1170 1170 1170 1170 1345 1345 1345
42C 1170 1170 1170 1170 1345 1345 1345
48C 1170 1170 1170 1170 1345 1345 1345
42D 1590 1590 1590 1590 1715 1715
48D 1590 1590 1590 1590 1715 1715 1715
60 1590 1590 1590 1590 1715 1715 1715
*ASPT
HEATER (Kw )
* Table applies t o ASPT* * 14* *
Table 6
35681015192025
29 715 715 715 715 875
39 1170 1170 1170 1170 1345 1345
49 1170 1170 1170 1170 1345 1345
59 1590 1590 1590 1590 1715 1715 1715
*ASUF
HEATER (Kw)
* Table applies t o ASUF* * 14* *
Table 7
M INIM UM CFM REQUIRED FOR HEATER KITS
12 Electrical and Control Wiring
IM PORTANT: All rout ing of elect rical wiring must be made through provided electrical knockouts. Do not cut , punct ure or alter the
cabinet for electrical wiring.
12.1 Building Electrical Service Inspection
This unit is designed for single-phase electrical supply only.
DO NOT OPERATE ON A THREE-PHASE POWER SUPPLY.
M easure the power supply to the unit. The supply volt age
must be measured and be in agreement with the unit
nameplat e power requirement s and wit hin the range
show n.
Nominal Input Minimum Voltage Maximum Voltage
208-240 197 253
ELECTRICAL VOLTAGE
Table 8