ASPT Service Manual
Table Of Contents
- IMPORTANT INFORMATION
- PRODUCT IDENTIFICATION
- Checking Voltage
- Checking Wiring
- Checking Thermostat And Wiring
- Thermostat Wiring
- Checking Transformer And Control Circuit
- Checking Contactor And/Or Relays
- Checking Contactor Contacts
- Checking Fan Relay Contacts
- Checking Loss Of Charge Protector (Heat Pump Models)
- Checking High Pressure Control
- Checking Low Pressure Control
- Copeland Comfort Alert™ Diagnostics - 3-Wire module
- Copeland Coresense™ Diagnostics - 3-Wire module
- Checking Capacitor
- Resistance Check Using A Digital Multi-Meter
- Capacitance Check Using A Digital Multi-Meter (In Capacitance Mode)
- Testing a Run Capacitor Under Load
- Checking Outdoor Fan and Blower Motors (PSC Motors)
- Checking Fan and Blower Motor (ECM Motors)
- Checking ECM Motor Windings
- ECM CFM Adjustments MBE/AEPF
- Blower Performance Data
- Checking High Efficiency Motors
- EEM Blower Replacement
- MBR/AR*F Electronic Blower Time Delay Relay
- Checking Compressor
- Resistance Test
- Ground Test
- Unloader Test Procedure
- Operation Test
- Checking 3-Phase Scroll Compressor Rotation
- Testing Crankcase Heater (Optional Item)
- Checking Reversing Valve and Solenoid
- Testing Defrost Control
- Testing Defrost Thermostat
- Checking Heater Limit Control(s)
- Checking Heater Elements
- Electric Heater (Optional Item)
- Checking Heater Limit Control(s)
- Checking Heater Elements
- Refrigeration Repair Practice
- Leak Testing (Nitrogen or Nitrogen-Traced)
- Evacuation
- Charging
- Checking Compressor Efficiency
- Overfeeding
- Underfeeding
- Checking Superheat
- Subcooling on Expansion Valve System
- Checking Expansion Valve Operation
- Checking Restricted Liquid Line
- Overcharge Of Refrigerant
- Non-Condensables
- Compressor Burnout
- Refrigerant Piping
- Duct Static Pressures
- Single Piece Air Handler External Static
- Two Piece Air Handler External Static Pressure
- Furnace External Static Pressure
- Periodic Maintenance
SERVICING
83
Blower Performance Data
The motor is a one piece, fully encapsulated, 3 phase
brushless DC (single phase AC input) motor with ball
bearing construction.
1. Using a voltmeter, check for 230 volts to the motor
connections L and N. If 230 volts is present, proceed to
step 2. If 230 volts is not present, check the line voltage
circuit to the motor.
2. Using a voltmeter, check for 24 volts from terminal C to
either terminal 1, 2, 3, 4, or 5, depending on which tap is
being used, at the motor. If voltage present, proceed tostep
3. If no voltage, check 24 volt circuit to motor.
3. If voltage was present in steps 1 and 2, the motor has
failed and will need to be replaced.
proper drip loop to prevent condensate from entering
the motor.
SP EED STATIC
MBR800**-*
SCFM
MBR1200**-*
SCFM
MBR1600**-*
SCFM
MBR2000**-*
SCFM
0.1 1,240 1,500 1,800 2,160
0.2 1,170 1,460 1,740 2,080
0.3 1,120 1,360 1,680 1,990
0.4 1,060 1,280 1,610 1,890
0.5 980 1,200 1,520 1,790
0.6 900 1,110 1,430 1,690
0.1 900 1,380 1,540 1,730
0.2 850 1,320 1,490 1,670
0.3 790 1,270 1,450 1,590
0.4 740 1,200 1,400 1,520
0.5 680 1,140 13,560 1,420
0.6 605 1,040 1,280 1,320
0.1 650 1,170 1,130 1,520
0.2 590 1,130 1,100 1,450
0.3 540 1,080 1,070 1,360
0.4 500 1,020 1,030 1,290
0.5 430 950 990 1,200
0.6 330 830 930 1,090
HIGH
MEDIUM
LOW
C
L G N
1 2 3
4
5
High Voltage
Connections
3/16"
Low Voltage Connections
1/4
Motor Connections