INSTALLATION & OPERATING INSTRUCTIONS AR090 & AR120 SERIES COMMERCIAL AIRHANDLER Goodman Manufacturing Company, LP 2550 North Loop West, Suite 400 Houston, TX 77092 USA IO-227 07/02
I II General Warnings WARNING Model Identification AR Before servicing or installing this equipment, the electrical power to this unit must be in the “OFF” position. Caution, more than one disconnect may exist. Failure to observe this warning may result in an electrical shock that can cause personnel injury.
IV. Unit Inspection The heating mode temperature rise is dependent upon the system airflow, the supply voltage, and the heat kit size (KW) selected. Use the following table to determine the temperature rise (oF): Upon delivery, the unit is to be inspected for damage. Any damage must be reported immediately to the carrier. Do not install this equipment if it is determined that the integrity or safety has been compromised by freight damage.
Location following sketch for further details: Dimensions are approx. 40” x 13-1/8” WARNING The AR series of airhandlers is designed for indoor installations only. DO NOT INSTALL OUTDOORS. WARNING When installing this airhandler in an enclosed area, such as a garage/parking area, with any carbon monoxide producing device (i.e. an automobile, space heater, water heater etc.) insure that the area is properly ventilated.
equipment S&R plate and the following table. WARNING AIR HANDLER AR090 To avoid the risk of fire or equipment damage use only copper conductors. VOLTAGE 208-230 WARNING 460 THIS PRODUCT IS CAPABLE OF USING EITHER 208230/3/60 OR 460/3/60 SUPPLY VOLTAGE. THIS AIR HANDLER IS FACTORY SHIPPED FOR USE WITH 208230/3/60 VOLTAGE. INSTALLATIONS USING 460/3/60 REQUIRING MODIFICATION TO THE MOTOR AND TRANSFORMER ELECTRICAL CIRCUITS. REFER TO THE “CONVERSION TO 460V POWER SUPPLY” SECTION OF THIS MANUAL.
AIR HANDLER AR090 AR120 X. Conversion Supply HEAT KIT None AHKD15-3 AHKD20-3 AHKD30-3 None AHKD15-4 AHKD20-4 AHKD30-4 None AHKD15-3 AHKD20-3 AHKD30-3 None AHKD15-4 AHKD20-4 AHKD30-4 460 MOP 15 60 70 100 15 30 35 50 15 60 70 100 15 30 35 50 Electrical Power AR120 Motor WARNING THIS PRODUCT IS CAPABLE OF USING EITHER 208230/3/60 OR 460/3/60 SUPPLY VOLTAGE. THE AIR HANDLER IS FACTORY SHIPPED FOR USE WITH 208230/3/60 VOLTAGE.
drawings for typical low voltage connections No Heat - Single Stage Cooling where R… Red, G… Green, BL…. Blue Note white wire and brown wire are not used and are to be taped. Supply Voltage - Heater Kit Models. When a heater kit is used the system uses a single point wiring hook-up. The supply wire is to be routed through conduit from the service disconnect box to the heater kit. The heat kit is equipped with a knockout suitable for ½” or ¾” conduit dependent on the KW.
• • • the CKL120 with the AR120 it is necessary to manifold the suction lines into a single connection. Similarly, the liquid lines of the AR120 are to be manifolded when matched with a single condenser/heat pump. See the following sketch for additional details. The model number agrees with the approved models (see the “Electric Heat” section of this manual). The correct size (kW) Electric characteristics, voltage and phase, agree with the building electrical supply.
T O S U C T IO N V A L V E # 1 O U T D O O R U N IT T O S U C T IO N V A L V E # 2 O U T D O O R U N IT • • rotate the other half clockwise (screw in). Tighten the set screw Reinstall the belt To decrease the airflow perform the same as above but rotate the sheave counterclockwise (screw out). T O L IQ U ID V A L V E # 1 O U T D O O R U N IT The following table can be used as guide for system airflow: T O L IQ U ID V A L V E # 2 O U T D O O R U N IT AR090 Static Pressure .1 .2 .3 .4 .
` 10