Submittal Sheet

Product sPEciFicAtions
SS-GMVC95 www.goodmanmfg.com 5


 
1 Electric Heat Mode
Select the taps allowed in the tables (Dipswitch 1/2/ 7/8) below.
2 Electric Heat Mode
3 N/A N/A
4 Thermostat Mode
ON = The system operates with single-stage units using a single-stage cooling or heat pump
thermostat. (factory default)
OFF = The system operates with two-stage units with either a convenonal two-stage cooling/
heat pump thermostat or with an encoded two-stage thermostat for cooling operaon.
The encoded thermostats can be used with two-stage condensing units in retrot applicaons where
there aren’t enough exisng wires available for connecons to the indoor thermostat and outdoor
units.
5 Cooling/Heat Pump Mode
Find the airow for your applicaon in the tables (Dipswitch 5/6/ 7/8) below. Set up the motor based
on the outdoor unit capacity tons.
6 Cooling/Heat Pump Mode
7 Trim CFM Adjust Mode Increase or decrease your selected airow to t your requirement.
ON-OFF = Increases selected Cool/Heat Pump airow by 10%.
OFF-ON = Decreases selected Cool/Heat Pump airow by 15%
Note: Other sengs have no eect on the set airow.
8 Trim CFM Adjust Mode
AEPF diPswitcHEs (cont.)
 
 









 
 
Up to 10 O O O O 1,100 1,210 2.5 O O O O 1,100 1,100
Up to 10 On O O O 890 935 2 On O O O 800 800
5 O On O O 700 770 1.5 O On O O 600 600
 









 
 
Up to 20 O O O O 2,050 2,150 5 O O O O 1,800 1,800
Up to 20 On O O O 1,750 1,835 4 On O O O 1,580 1,580
Up to 15 O On O O 1,600 1,680 3.5 O On O O 1,480 1,480
Up to 10 On On O O 1,200 1,260 3 On On O O 1,200 1,200
Up to 10 On On O On 1,020 1,070 2.5 On On O On 1,020 1,020
 









 
 
Up to 15 O On O O 1,600 1,680 3.5 O On O O 1,480 1,480
Up to 10 On On O O 1,200 1,260 3 On On O O 1,200 1,200
Up to 10 On On O On 1,020 1,070 2.5 On On O On 1,020 1,020
 When applying a humidistat (normally closed), refer to the installaon and operang instrucons.
The humidistat can adjust the cooling airow to 85%.