Instructions / Assembly

SERVICING
78
Symptoms of Abnormal Operation
(Legacy & ComfortNet Thermostat)
Diagnostic/Status LED Codes
Faul t
Description
Comf or t N e t
Thermostat Only
Possible Causes
Corrective Actions Notes & Cautions
Green Yel lo w Red Red Y1 Me ss age Code
Very long run time.
Four consecutive compressor protector
trips with average run time between
trips greater than 3 hours.
Compressor operating at high speed
and outdoor fan operating at low speed
Integrated control module
diagnostic/status LEDs display the
indicated code.
OFF 1 Flash OFF ON if call
present;
OFF if no
call
Low Side Fault. LOW S IDE
FAULT
01 Low refrigerant charge.
Restriction in liquid line.
Indoor blower motor
failure.
Indoor thermostat set
extremely low.
Verify refrigerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Fault will clear after 30
consecutive normal
cycles.
Faul t may be cleared by
cycling 24VAC to
control.
Replace with correct
replacement part(s).
Compressor a nd outdoor fan are off.
Thermostat demand is present.
Integrated control module
diagnostic/status LEDs display the
indicated code.
ON 1 Flash OFF ON if call
present;
OFF if no
call
Low Pressure
CO Trip.
LPS OPEN 01
Low refrigerant charge.
Restriction in liquid line.
Indoor blower motor
failure.
Indoor thermostat set
extremely low.
Verify refrigerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check low pressure
switch; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Replace with correct
replacement part(s).
Compressor a nd outdoor fan are off.
Low pressure switch trip 3 times within
same thermostat demand.
Thermostat demand is present.
Integrated control module
diagnostic/status LEDs display the
indicated code.
ComfortNet™ thermostat “Call for
Service” icon illuminated.
ComfortNet™ thermostat scrolls
Check Air Conditioner” orCheck
Heat Pump” message.
ON 1 Flash ON ON if call
present;
OFF if no
call
LPCO Lockout
(3 Trips).
LPS
LOCKOUT
01
Low refrigerant charge.
Restriction in liquid line.
Indoor blower motor
failure.
Indoor thermostat set
extremely low.
Verify refrigerant
charge; adjust as
needed.
Check for restricted
liquid line;
repair/replace as
needed.
Check indoor blower
motor; repair/replace
as needed.
Check low pressure
switch; repair/replace
as needed.
Check indoor
thermostat setting.
Turn power OFF prior
to repair.
Must clear fault by
cycling 24VAC to
control.
Replace with correct
replacement part(s).