- Goodman Mfg. Co. LP. Air Conditioner User Manual
ProdUCt sPeCiFiCations
ProdUCt sPeCiFiCations
SS-CPG36-72 www.goodmanmfg.com 7
ProdUCt sPeCiFiCations — CPG060 B models
CPG060
0901DXXX
CPG060
0903DXXX
CPG060
0903BXXX
CPG060
0904BXXX
Total BTU/h 59,500 59,500 59,500 59,500
Sensible BTU/h 43,200 43,200 43,200 43,200
SEER / EER 13 / 11.3 13 / 11.3 13 / 11.3 13 / 11.3
Decibels 78 78 78 78
ARI Reference Nos. 4385065 4385066 4385066 4385067
Max. Input /Output kBTU/h 92 / 74 92 / 74 92 / 74 92 / 74
Low Input /Output kBTU/h 69 / 55 69 / 55 69 / 55 69 / 55
Steady State Eciency (AFUE) 80 80 80 80
Temperature Rise Range (°F) 20-50 / 15-45 20-50 / 15-45 20-50 / 15-45 20-50 / 15-45
No. of Burners 4 4 4 4
Motor Type Direct Direct Belt Belt
Indoor Nominal CFM 2,000 2,000 2,000 2,000
Piston Size (Cooling) 0.086 0.086 0.086 0.086
Filter Size (#) 14 x 20 x 2 (4) 14 x 20 x 2 (4) 14 x 20 x 2 (4) 14 x 20 x 2 (4)
Drain Size (NPT) ¾” ¾” ¾” ¾”
R-410A Refrigerant Charge (oz.) 162 162 162 165
Face Area (²) 7.8 7.8 7.8 7.8
Rows Deep/ Fins per Inch 4 / 16 4 / 16 4 / 16 4 / 16
Tube Diameter - Material 5/16 - Copper 5/16 - Copper 5/16 - Copper 5/16 - Copper
# of Wheels (D x W) --- --- 1 (11” x 10”) 1 (11” x 10”)
Motor Sheave / Blower Sheave --- --- VL44 X ⅝ / AK61 X 1
Belt --- --- AX53 AX53
Horsepower / RPM ¼ / 1,090 ¼ / 1,090 ¼ / 1,090 ¼ / 1,090
Fan Diameter/ # Fan Blades 22 / 4 22 / 4 22 / 4 22 / 4
Outdoor Nominal CFM 3,800 3,800 3,800 3,800
Face Area (²) 17.0 17.0 17.0 17.0
Rows Deep/ Fins per Inch 2 / 18 2 / 18 2 / 18 2 / 18
Tube Diameter - Material 5/16 - Copper 5/16 - Copper 5/16 - Copper 5/16 - Copper
Quanty / Stage 1 / Single 1 / Single 1 / Single 1 / Single
Type Scroll Scroll Scroll Scroll
Compressor RLA / LRA 26.4 / 134 16 / 110 16 / 110 7.8 / 52
Voltage-Phase-Frequency 208/230-1-60 208/230-3-60 208/230-3-60 460-3-60
Indoor Blower HP / FLA )STD Stac) 1.0 / 7.6 1.0 / 7.6 1.0 / 3.8 1.0 / 1.9
Indoor Blower LRA ---- ---- 24 13
Outdoor Fan HP / FLA ¼ / 1.40 ¼ / 1.40 ¼ / 1.40 ¼ / 0.8
Min. Circuit Ampacity¹ 42 29 25 13
Max. Overcurrent Protecon (amps)² 60 45 40 20
Power Supply Conduit Hole 1.125 1.125 1.125 1.125
Low-Voltage Conduit Hole ½” ½” ½” ½”
620 620 620 620
645 645 645 645
¹WiresizeshouldbedeterminedinaccordancewithNationalElectricalCodes.Extensivewirerunswillrequirelargerwiresizes.
²MayusefusesorHACR-typecircuitbreakersofthesamesizeasnoted.
Note:AlwayschecktheS&Rplateforelectricaldataontheunitbeinginstalled.