- Goodman Mfg. Co. LP. Air Conditioner User Manual
ProdUCt sPeCiFiCations
ProdUCt sPeCiFiCations
4 www.goodmanmfg.com SS-CPG36-72
ProdUCt sPeCiFiCations — CPG036 B models (Cont.)
CPG036
0901DXXX
CPG036
0903DXXX
CPG036
0903BXXX
CPG036
0904BXXX
CPG036
0907BXXX
Total BTU/h 34,600 34,600 34,600 34,600 35,000
Sensible BTU/h 25,600 25,600 25,600 25,600 25,900
SEER / EER 13 / 11.3 13 / 11.3 13 / 11.3 13 / 11.3 13 / 11.3
Decibels 78 78 78 78 78
AHRI #s 4385059 4385060 4385060 4385061 4397607
Hi. Input / Output BTU/h 92 / 74 92 / 74 92 / 74 92 / 74 92 / 74
Low. Input / Output kBTU/h 69 / 55 69 / 55 69 / 55 69 / 55 69 / 55
Steady State Eciency (AFUE) 80 80 80 80 80
Temperature Rise Range (°F) Hi / Low 40-70 / 30-60 40-70 / 30-60 40-70 / 30-60 40-70 / 30-60 40-70 / 30-60
No. of Burners 4 4 4 4 3
Motor Type Direct Drive Direct Drive Belt Drive Belt Drive Belt Drive
# of Wheels (D x W) 1 (10” x 9”) 1 (10” x 9”) 1 (11” x 10”) 1 (11” x 10”) 1 (11” x 10”)
Indoor Nominal CFM 1,200 1,200 1,200 1,200 1,200
Motor Speed Tap (Cooling) Low Speed Low Speed --- --- ---
Indoor Motor FLA (Cooling) 2.50 2.50 3.8 1.9 1.9
Horsepower - RPM ⅓ - 890 ⅓ - 890 1.0 - 1,725 1.0 - 1,725 1.0 - 1,725
Piston Size (Cooling) 0.068 0.068 0.068 0.068 0.068
Filter Size (“) (1) 24 x 24 x 2 (1) 24 x 24 x 2 (1) 24 x 24 x 2 (1) 24 x 24 x 2 (1) 24 x 24 x 2
Drain Size (NPT) ¾” ¾” ¾” ¾” ¾”
R-410A Refrigerant Charge Cir #1(oz.) 90 83 83 90 90
Evaporator Coil Face Area (²) 5.4 5.4 5.4 5.4 5.4
Rows Deep / Fins per Inch 3 / 16 3 / 16 3 / 16 3 / 16 3 / 16
# of Wheels (D x W) --- --- 1 (11” x 10”) 1 (11” x 10”) 1 (11” x 10”)
Motor Sheave / Blower Sheave --- --- 1VL40 X ⅝ / AK69 X 1
Belt --- --- AX55 AX55 AX55
Quanty of Condenser Fan Motors 1 1 1 1 1
Horsepower - RPM ¼ / 1,090 ¼ / 1,090 ¼ / 1,090 ¼ - 890 ¼ - 1,075
Fan Diameter/ # Fan Blades 22 / 4 22 / 4 22 / 4 22 / 4 22 / 4
Outdoor Nominal CFM 3,800 3,800 3,800 3,800 3,800
Face Area (²) 18.0 18.0 18 18 13
Rows Deep/ Fins per Inch 1 / 22 1 / 22 1 / 22 1 / 22 2 / 16
Quanty / Stage 1 / Single 1 / Single 1 / Single 1 / Single 1 / Single
Type Scroll Scroll Scroll Scroll Scroll
Compressor RLA / LRA 16.7 / 79.0 10.4 / 73.0 10.4 / 73.0 5.8 / 38.0 3.8 / 36.5
Voltage-Phase-Frequency 208/230-1-60 208/230-3-60 208/230-3-60 460-3-60 575-3-60
Indoor Blower HP / FLA ⅓ / 2.5 ⅓ / 2.5 1 / 3.8 1 / 1.9 1 / 1.9
Outdoor Fan HP / FLA ¼ / 1.4 ¼ / 1.4 ¼ / 1.4 ¼ / 0.8 ¼ / 0.8
Total Unit Amps 20.57 14.35 15.65 8.47 6.68
Min. Circuit Ampacity¹ 25 17 18 10 8
Max. Overcurrent Protecon (amps)² 40 25 25 15 15
Power Supply Conduit Hole 1.125 1.125 1.125 1.125 1.125
Low-Voltage Conduit Hole ½” ½” ½” ½” ½”
535 535 535 535 535
560 560 560 560 560
¹WiresizeshouldbedeterminedinaccordancewithNationalElectricalCodes.Extensivewirerunswillrequirelargerwiresizes.
²MayusefusesorHACR-typecircuitbreakersofthesamesizeasnoted.
Note:AlwayschecktheS&Rplateforelectricaldataontheunitbeinginstalled.