- Goodman Mfg. Co. LP. Air Conditioner User Manual

Product SPecificationS
Product SPecificationS
SS-CPG36-72 www.goodmanmfg.com 33
Wiring diagram cPg036.48*3d (three-PhaSe direct drive)
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
Warning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
2. FOR 208 VOLT TRANSFORMER OPERATION
MOVE BLACK WIRE FROM TERMINAL 3 TO
TERMINAL 2 ON TRANSFORMER.
1. REPLACEMENT W IRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).
AUXILLARY LIMIT SWITCH
FEMALE PLUG/CONNECTOR
INTEGRATED IGNITION CONTROL
LS
4
INSTALLER/S ERVICEMAN
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
STATUS LIGHT
3 BLINKS
6 BLINKS
2 BLINKS
4 BLINKS
5 BLINKS
OFF
ON
1 BLINK
OPEN AUX. LIMIT
FALSE FLAME SENSED
OUTPUT DELAY
OPEN LIMIT SWITCH
COMPRESSOR
WITHOUT INDUCER ON
PRESSURE SWITCH CLOSED
PRESSURE SWITCH
SWITCH
OPEN
OPEN ROLLOUT
SWITCH
IGNITION FAILURE
NORMAL OPERATION
NO POWER OR
INTERNAL CONTROL
EQUIP. STATUS
OR
OR
FAULT
TO THERMOSTAT
TERMINAL BLOCK
GR
5
7
9
ECON
IIC
Y1
W Y2
3
6
12
10
8
11
RS
ALS
PS
BAD SWITCH
AUX. LIMIT OPEN
ANTI-CYCLE TIMER
MAIN LIMIT OPEN
STICKING GAS VALVE
BAD SWITCH
3 MIN. COMP.
PRESSURE SWITCH
PRESSURE SWITCH
CHECK
CHECK
GAS PRESSURE
FLAME ROLLOUT
FLAME SENSOR
GAS VALVE
CHECK FUSE ON CONTROL
CHECK INPUT POWER
REPLACE CONTROL
GAS FLOW
CHECK
-
PLF
C
NOTE
4
4
321
56
GV
C
L1
208-240/3/60
SUPPLY VOLTAGE
CM
CONDENSER MOTOR
L3
LS LIMIT SWITCH
VENT MOTOR RELAY
VENT MOTOR
PRESSURE SWITCH
TERMINAL BLOCK (24V SIGNAL)
ROLLOUT SWITCH
VMR
VM
PS
PLF
TB1
RS
N
OTES
FAN CAPACITOR
CONTACTOR
GAS VALVE
IGNITOR
EQUIPMENT GROUND
FLAME SENSOR
EVAPORATOR MOTOR
FC
FUSE
F
C
GV
FS
GND
IGN
IIC
EM
L2 L3
COMPRESSOR
C
OMPONENT LEGEND
COMP
ALS
TB1
TR
TRANSFORMER
L2
C
CM
T3
COMP
T3
T2
FC
L1
C
T1
T1
C
T2
208-240/3/60 0140L00512 REV B
HPS
LPS
LPS LOW PRESSURE SWITCH
HPS HIGH PRESSURE SWITCH
HIGH VOLTAGE
FACTORY WIRING
OPTIONAL
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
LINE VOLTAGE
LOW VOLTAGE
BL
RD
Y1
Y/Y2
YL
W
Y/Y2
BL
G
R
W
NO ECO
NOMIZER
G
YL
RD
Y/Y2
Y1
PK
WH
W
R
RD
WH
GR
C
R
YL
GR
Y1
G
WH
W
ITH ECONOMIZER OPTION
C
GR
THERMOSTAT
FIELD WIRING
BL
C
2S
TAGE COOLING
TB1
G
R
W
Y
C
TB1
TB1
Y
W
R
G
C
W
Y2
G
R
C
Y1
STAT
STAT
STAT
BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP
GR GREEN
W
IRE CODE
BL BLUE
PU PURPLE
PK PINK
WH WHITE
BK BLACK
RD RED
BR BROWN
OR ORANGE
YL YELLOW
EM
DI
PCB
HE AT
COOL
FC
PCB
LI
TB1
IIC
FS
TR
FS
F
IGN
SEE NOTE 2
2
13
VM
3. FOR DIFFERENT THAN FACTORY SPEED TAP.
CHANGE COOLING SPEED AT COOL
TERMINAL. CHANGE HEATING SPEED AT
HEAT TERMINAL ON CONTROL BOARD
BK - HIGH SPEED
BL - MED. SPEED
RD - LOW SPEED
3 SPEE
D MOTOR
4. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO ECONOMIZER
ACCESSORY.
USE NEC CLASS 2 WIRE.
5. USE COPPER CONDUCTORS ONLY.
7. SPEED TAP TERMINATIONS SHOWN ON
DIAGRAM ARE REPRESENTATIVE, BUT ACTUAL
FACTORY SETTING MAY BE DIFFERENT BASED
ON HEATING VALUE AND CAPACITY OF UNIT.
6. PURPLE WIRE CONNECTS TO TRANSFORMER
(PIN 1).
BLOWER CAPACITOR
BC
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF
OVERCURRENT PROTECTION.
8. TO RUN DIFFERENT SPEED FOR HEATING AND
COOLING, DISCONNECT GEEEN JUMPER FROM
"COOL" TERMINAL AND REPLACE WITH
APPROPRIATE SPEED TAP. THEN PLACE
DISCONNECTED END OF JUMPER ON
"UNUSED" TERMINAL LEFT OPEN BY MOVING
THE SPEED TAP.