- Goodman Mfg. Co. LP. Air Conditioner User Manual

ProdUCt sPeCiFiCations
ProdUCt sPeCiFiCations
SS-CPG36-72 www.goodmanmfg.com 27
rooF CUrB installation — riGGinG
Provisionsforforkshavebeenincludedintheunitbaseframe.Nootherfork
locationsareapproved.
• Unitmustbeliftedbythefourliftingholeslocatedatthebaseframe
corners.
• Liftingcablesshouldbeattachedtotheunitwithshackles.
• Thedistancebetweenthecranehookandthetopoftheunitmustnotbe
lessthan60”.
• Twospreaderbarsmustspanovertheunittopreventdamagetothecabi-
netbytheliftcables.Spreaderbarsmustbeofsufcientlengthsothatca-
blesdonotcomeincontactwiththeunitduringtransport.Removewood
strutsmountedbeneathunitbaseframebeforesettingunitonroofcurb.
Thesestrutsareintendedtoprotectunitbaseframefromforkliftdamage.
Toremovethestruts,extractthesheetmetalretainersandpullthestruts
throughthebaseoftheunit.Refertorigginglabelontheunit.
Important: If using bottom discharge with roof curb, duct-work should be
attachedtothecurbpriortoinstallingtheunit.Duct-workdimensionsare
showninRoofCurbInstallationInstructionsManual.
RefertotheRoofCurbInstallationInstructionsforpropercurbinstallation.
CurbingmustbeinstalledincompliancewiththeNationalRoongContractorsAssociationManual.
Lowerunitcarefullyontoroofmountingcurb.Whileriggingtheunit,thecenterofgravitywillcausethecondenserendtobelower
thanthesupplyairend.
Bringcondenserendofunitintoalignmentwiththecurb.Withcondenserendoftheunitrestingoncurbmemberandusingcurbas
afulcrum,loweroppositeendoftheunituntilentireunitisseatedonthecurb.Whenarectangularcantilevercurbisused,takecare
tocentertheunit.Checkforproperalignmentandorientationofsupplyandreturnopeningswithduct.
Corner & Center-oF-Gravity loCations
30”
Compressor
Return
Evaporator Coil
Supply
Condenser
Coil
37”









Corner Weight (A)
100 110 115
130
Corner Weight (B)
170 180 195
215
Corner Weight (C)
105 110 120
130
Corner Weight (D)
170 180 195
215
Unit Shipping Weight 550 595 625 715
Unit Operang Weight 525 570 600 690
Note: Weights are calculated without accessories installed.