- Goodman Mfg. Co. LP. Air Conditioner User Manual
24
APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE
HIGH STATIC HORIZONTAL
CPC/H036 HIGH STATIC BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
1742 0.50 1 4 31 0.3 6
0.8
1626 0.52 1357 0.39 1078 0.27
1
1611 0.56 1315 0.42 1011 0.28
1.2
1605 0.62 1299 0.46 976 0.31
1.4
1605 0.68 1281 0.51 959 0.35
1.6
1281 0 .57 981 0.41
1.8
981 0 .47
CPC/H048 HIGH STATIC BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
2056 0.72 1 7 21 0.5 4
0.8
1996 0.77 1662 0.57 1328 0.40
1
1924 0.79 1603 0.61 1270 0.43
1.2
1952 0.88 1559 0.64 1210 0.44
1.4
1888 0.92 1543 0.70 1195 0.49
1.6
1557 0.77 1180 0.54
1.8
1192 0 .60
CPC/H060 HIGH STATIC BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
23 23 0.9 2
0.8
2315 1.00 2 0 09 0.7 7
1
2308 1.09 1992 0.84 1666 0.60
1.2
2338 1.21 1992 0.92 1646 0.66
1.4
2359 1.32 2025 1.02 1648 0.72
1.6
2404 1.45 2056 1.13 1684 0.82
1.8
2088 1.24 1722 0.92
CPC/H072 HIGH STATIC BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
2746 1.38 2 5 15 1.1 2
0.8
2721 1.47 2494 1.21 2261 0.97
1
2689 1.56 2500 1.32 2255 1.06 1994 0.83
1.2
2752 1.74 2473 1.40 2252 1.15 1996 0.91
1.4
2802 1.88 2487 1.53 2286 1.27 2037 1.02
1.6
2553 1.67 2308 1.40 1997 1.08
1.8
2355 1.51 2014 1.19
2.0
2055 1 .29
NOTES:
ESP, In
H
2
O
TU RNS OPEN
012345
ESP, In
H
2
O
TU RNS OPEN
012345
ESP, In
H
2
O
TU RNS OPEN
012345
Tables represent dry coil without filter, to co mpensate f or f ilter add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4 %.
ESP, In
H
2
O
TU RNS OPEN
012345