- Goodman Mfg. Co. LP. Heat Pump User Manual
prodUCt speCifiCations
prodUCt speCifiCations
28 www.goodmanmfg.com SS-GPH15M
airflow data
Model
Motor
Tap Speed
Volts
E.S.P (In. of H
2
O)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
GPH15
24M41A*
T1 (G) 230
CFM 882 808 727 649 545 --- --- ---
Was 82 86 92 102 108 --- --- ---
T2 / T3 (W2) 230
CFM 933 873 810 733 637 584 --- ---
Was 93 103 109 120 126 135 --- ---
T4 / T5 (Y) 230
CFM 1058 1012 945 896 816 723 672 ---
Was 124 136 142 153 168 172 179 ---
GPH15
30M41A*
T1 (G) 230
CFM 893 824 752 665 575 --- --- ---
Was 87 95 101 111 115 --- --- ---
T2 / T3 (W2) 230
CFM 1132 1070 1011 959 889 827 733 669
Was 153 162 168 179 184 195 206 208
T4 / T5 (Y) 230
CFM 1287 1236 1165 1123 1066 1012 958 857
Was 211 217 228 239 244 255 265 272
GPH15
36M41A*
T1 (G) 230
CFM 852 764 711 592 545 - - -
Was 80 82 86 95 99 - - -
T2 / T3 (W2) 230
CFM 1232 1190 1131 1082 1023 966 889 819
Was 202 214 221 229 235 246 258 264
T4 / T5 (Y) 230
CFM 1267 1213 1162 1120 1058 1009 932 841
Was 218 226 236 245 247 260 272 275
GPH15
42M41A*
T1 (G) 230
CFM 893 830 741 619 557 --- --- ---
Was 89 99 104 117 131 --- --- ---
T2 / T3 (W2) 230
CFM 1393 1339 1297 1230 1180 1116 1056 901
Was 271 280 292 300 310 320 324 329
T4 / T5 (Y) 230
CFM 1511 1464 1422 1355 1313 1184 1064 983
Was 345 354 364 381 390 392 375 360
G = Fan only W2 = Heat mode Y = Cooling mode
Notes
• Data shown is dry coil. Wet coil pressure drop is approximately 0.1" H2O, for two-row indoor coil; 0.2” H2O, for three-row indoor coil; and 0.3” H2O, for
four-row indoor coil.
• Data shown does not include lter pressure drop, approx. 0.08” H2O.
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON. USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM. See Repair Parts list.
• Reduce airow by 2% for 208-volt operaon.