- Goodman Mfg. Co. LP. Heat Pump User Manual

prodUCt speCifiCations
prodUCt speCifiCations
14 www.goodmanmfg.com SS-GPH15M
expanded Cooling datagph1543m41a*
Outdoor Ambient Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
70
1400
MBh 39.2 40.7 44.5 - 38.3 39.7 43.5 - 37.4 38.8 42.5 - 36.5 37.8 41.4 - 34.7 35.9 39.4 - 32.1 33.3 36.5 -
S/T 0.70 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.62 0.43 - 0.77 0.64 0.45 - 0.80 0.67 0.46 - 0.81 0.67 0.47 -
T 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
kW 2.51 2.57 2.65 - 2.71 2.77 2.85 - 2.88 2.94 3.04 - 3.03 3.10 3.20 - 3.16 3.23 3.33 - 3.27 3.34 3.45 -
Amps 11.9 12.2 12.5 - 12.8 13.0 13.4 - 13.7 14.0 14.4 - 14.5 14.8 15.3 - 15.3 15.7 16.1 - 16.1 16.5 17.0 -
HI PR 228 245 259 - 256 275 291 - 291 313 331 - 331 357 377 - 373 401 424 - 412 443 468 -
LO PR 107 114 124 - 113 120 131 - 118 125 136 - 123 131 143 - 129 138 150 - 134 142 155 -
1250
MBh 38.1 39.5 43.2 - 37.2 38.5 42.2 - 36.3 37.6 41.2 - 35.4 36.7 40.2 - 33.7 34.9 38.2 - 31.2 32.3 35.4 -
S/T 0.67 0.56 0.39 - 0.69 0.58 0.40 - 0.71 0.59 0.41 - 0.74 0.61 0.43 - 0.76 0.64 0.44 - 0.77 0.64 0.45 -
∆T 19 16 12 - 19 16 12 - 19 16 12 - 19 17 13 - 19 16 12 - 18 15 12 -
kW 2.49 2.55 2.63 - 2.69 2.74 2.83 - 2.85 2.92 3.01 - 3.00 3.07 3.17 - 3.13 3.20 3.31 - 3.24 3.31 3.42 -
Amps 11.8 12.1 12.4 - 12.7 12.9 13.3 - 13.6 13.9 14.3 - 14.4 14.7 15.1 - 15.2 15.5 16.0 - 16.0 16.4 16.9 -
HI PR 226 243 257 - 253 273 288 - 288 310 327 - 328 353 373 - 369 397 419 - 408 439 463 -
LO PR 106 113 123 - 112 119 130 - 116 124 135 - 122 130 142 - 128 136 149 - 132 141 154 -
1200
MBh 37.7 39.1 42.8 - 36.8 38.2 41.8 - 35.9 37.3
40.8 - 35.1 36.3 39.8 - 33.3 34.5 37.8 - 30.9 32.0 35.0 -
S/T 0.66 0.55 0.38 - 0.69 0.57 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.76 0.64 0.44 -
∆T 19 17 13 - 19 17 13 - 19 17 13 - 20 17 13 - 19 17 13 - 18 16 12 -
kW 2.47 2.52 2.60 - 2.66 2.71 2.80 - 2.82 2.89 2.98 - 2.97 3.04 3.14 - 3.10 3.17 3.27 - 3.20 3.28 3.38 -
Amps 11.7 12.0 12.3 - 12.5 12.8 13.1 - 13.5 13.7 14.1 - 14.3 14.6 15.0 - 15.1 15.4 15.8 - 15.8 16.2 16.7 -
HI PR 223 240 253 - 250 269 284 - 284 306 323 - 324 348 368 - 364 392 414 - 403 433 457 -
LO PR 105 111 121 - 110 118 128 - 115 122 133 - 121 128 140 - 126 134 147 - 131 139 152 -
75
1400
MBh 39.9 41.1 44.5 47.7 39.0 40.1 43.4 46.6 38.0 39.2 42.4 45.5 37.1 38.2 41.3 44.4 35.2 36.3 39.3 42.2 32.7 33.6 36.4 39.1
S/T 0.80 0.71 0.54 0.35 0.83 0.74 0.56 0.36 0.85 0.76 0.57 0.37 0.88 0.78 0.59 0.38 0.91 0.81 0.62 0.40 0.92 0.82 0.62 0.40
∆T 21 19 16 11 21 20 16 11 21 20 16 11 21 20 16 11 21 19 16 11 20 18 15 10
kW 2.53 2.59 2.67 2.76 2.73 2.79 2.88 2.97 2.90 2.97 3.06 3.16 3.05 3.12 3.22 3.33 3.18 3.25 3.36 3.48 3.30 3.37 3.48 3.60
Amps 12.0 12.3 12.6 13.0 12.9 13.1 13.5 13.9 13.8 14.1 14.5 15.0 14.6 15.0 15.4 15.9 15.5 15.8 16.3 16.8 16.3 16.6 17.1 17.7
HI PR 230 248 262 273 258 278 294 306 294 316 334 348 335 360 380 397 377 405 428 446 416 448 473 493
LO PR 108 115 126 134 114 122 133 141 119 126 138 147 125 133 145 154 131 139 152 162 135 144 157 167
1250
MBh 38.7 39.9 43.2 46.3 37.8 38.9 42.2 45.2 36.9 38.0 41.1 44.2 36.0 37.1 40.1 43.1 34.2 35.2 38.1 40.9 31.7 32.6 35.3 37.9
S/T 0.76 0.68 0.52 0.33 0.79 0.71 0.53 0.34 0.81 0.72 0.55 0.35 0.84 0.75 0.57 0.36 0.87 0.78 0.59 0.38 0.87 0.78 0.59 0.38
∆T 22 20 16 11 22 20 17
11 22 20 17 11 22 20 17 12 22 20 16 11 20 19 15 11
kW 2.51 2.57 2.65 2.73 2.71 2.77 2.86 2.95 2.88 2.94 3.04 3.14 3.03 3.10 3.20 3.31 3.16 3.23 3.33 3.45 3.27 3.34 3.45 3.57
Amps 11.9 12.2
12.5 12.9 12.8 13.0 13.4 13.8 13.7 14.0 14.4 14.9 14.5 14.8 15.3 15.8 15.3 15.7 16.1 16.7 16.1 16.5 17.0 17.6
HI PR 228 245 259 270 256 275 291 303 291 313 331 345 331 357 377 393 373 401 424 442 412 443 468 488
LO PR 107 114 124 132 113 120 131 140 118 125 137 145 123 131 143 153 129 138 150 160 134 142 155 166
1200
MBh 38.3 39.5 42.7 45.9 37.4 38.6 41.7 44.8 36.6 37.6 40.7 43.7 35.7 36.7 39.7 42.7 33.9 34.9 37.8 40.5 31.4 32.3 35.0 37.5
S/T 0.75 0.67 0.51 0.33 0.78 0.70 0.53 0.34 0.80 0.72 0.54 0.35 0.83 0.74 0.56 0.36 0.86 0.77 0.58 0.37 0.87 0.77 0.59 0.38
∆T 22 20 17 12 22 21 17 12 22 21 17 12 23 21 17 12 22 21 17 12 21 19 16 11
kW 2.49 2.54 2.62 2.71 2.68 2.74 2.82 2.92 2.85 2.91 3.00 3.10 3.00 3.06 3.16 3.27 3.12 3.19 3.30 3.41 3.23 3.30 3.41 3.53
Amps 11.8 12.1 12.4 12.8 12.6 12.9 13.3 13.7 13.6 13.8 14.2 14.7 14.4 14.7 15.1 15.6 15.2 15.5 16.0 16.5 16.0 16.3 16.8 17.4
HI PR 225 242 256 267 253 272 287 299 287 309 326 340 327 352 372 388 368 396 418 436 407 438 462 482
LO PR 106 112 123 131 112 119 130 138 116 123 135 144 122 130 142 151 128 136 148 158 132 141 153 163
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions kW = Total system power
High & low pressures are measured at the liquid & sucon access ngs. Amps = outdoor unit amps (comp.+ fans)