- Goodman Mfg. Co. LP. Heat Pump User Manual

prodUCt speCifiCations
prodUCt speCifiCations
SS-GPH15M www.goodmanmfg.com 11
expanded Cooling datagph1542m41a* – low stage (Cont.)
Outdoor Ambient Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
80
955
MBh 27.9 28.5 30.4 32.6 27.2 27.8 29.7 31.8 26.6 27.2 29.0 31.0 25.9 26.5 28.3 30.3 24.6 25.2 26.9 28.8 22.8 23.3 24.9 26.6
S/T 0.88 0.82 0.67 0.50 0.91 0.85 0.69 0.52 0.93 0.87 0.71 0.53 0.96 0.90 0.74 0.55 1.00 0.94 0.76 0.57 1.00 0.95 0.77 0.57
∆T 24 23 20 16 24 23 20 16 24 23 20 16 24 23 20 16 24 23 20 16 22 21 18 15
kW 1.83 1.87 1.93 2.00 1.98 2.02 2.09 2.16 2.11 2.16 2.23 2.31 2.22 2.28 2.35 2.44 2.32 2.38 2.46 2.54 2.41 2.46 2.55 2.64
Amps 7.9 8.0 8.3 8.6 8.4 8.6 8.9 9.2 9.1 9.3 9.6 10.0 9.7 9.9 10.3 10.6 10.3 10.6 10.9 11.3 10.9 11.2 11.5 11.9
Hi PR 223 240 253 264 250 269 284 296 284 306 323 337 324 348 368 383 364 392 414 431 402 433 457 477
Lo PR 109 116 127 135 116 123 134 143 120 128 139 148 126 134 146 156 132 141 153 163 137 145 159 169
850
MBh 27.1 27.7 29.6 31.6 26.4 27.0 28.9 30.9 25.8 26.4 28.2 30.1 25.2 25.7 27.5 29.4 23.9 24.5 26.1 27.9 22.2 22.7 24.2 25.9
S/T 0.84 0.79 0.64 0.48 0.87 0.81 0.66 0.50 0.89 0.83 0.68 0.51 0.92 0.86 0.70 0.52 0.95 0.89 0.73 0.54 0.96 0.90 0.73 0.55
∆T 25 23 20 16 25 24 21 17 25 24 21 17 25 24 21 17 25 24 21 16 23 22 19 15
kW 1.82 1.86 1.92 1.98 1.96 2.01 2.07 2.14 2.09 2.14 2.21 2.29 2.21 2.26 2.33 2.41 2.30 2.36 2.44 2.52 2.39 2.44 2.53 2.61
Amps 7.8 8.0 8.2 8.5 8.4 8.6 8.8 9.1 9.1 9.3 9.5 9.9 9.6 9.9 10.2 10.5 10.2 10.5 10.8 11.2 10.8 11.1 11.4 11.8
Hi PR 220 237 250 261 247 266 281 293 281 303 320 333 320 345 364 380 360 388 410 427 398 428 452 472
Lo PR 108 115 126 134 114 122 133 141 119 126 138 147 125 133 145 154 131 139 152 162 135 144 157 167
745
MBh 25.0 25.5 27.3 29.2 24.4 24.9 26.7 28.5 23.8 24.4 26.0
27.8 23.3 23.8 25.4 27.1 22.1 22.6 24.1 25.8 20.5 20.9 22.3 23.9
S/T 0.81 0.76 0.62 0.46 0.84 0.78 0.64 0.48 0.86 0.80 0.65 0.49 0.89 0.83 0.68 0.51 0.92 0.86 0.70 0.52 0.93 0.87 0.71 0.53
∆T 25 24 21 17 25 24 21 17 25 24 21 17 25 24 21 17 25 24 21 17 23 22 20 16
kW 1.77 1.81 1.87 1.93 1.91 1.95 2.02 2.09 2.04 2.08 2.15 2.23 2.15 2.20 2.27 2.35 2.24 2.29 2.37 2.46 2.32 2.38 2.46 2.55
Amps 7.6 7.8 8.0 8.3 8.2 8.3 8.6 8.9 8.8 9.0 9.3 9.6 9.4 9.6 9.9 10.3 10.0 10.2 10.5 10.9 10.5 10.8 11.1 11.5
Hi PR 214 230 243 253 240 258 273 284 273 294 310 323 311 334 353 368 350 376 397 414 386 416 439 458
Lo PR 105 112 122 130 111 118 129 137 115 123 134 143 121 129 141 150 127 135 147 157 131 140 152 162
85
955
MBh 28.4 28.9 30.3 32.3 27.7 28.3 29.6 31.6 27.1 27.6 28.9 30.8 26.4 26.9 28.2 30.1 25.1 25.6 26.8 28.6 23.2 23.7 24.8 26.5
S/T 0.92 0.89 0.80 0.65 0.95 0.92 0.83 0.67 0.98 0.94 0.85 0.69 1.00 0.97 0.88 0.71 1.00 1.00 0.91 0.74 1.00 1.00 0.92 0.75
∆T 25 25 23 20 25 25 24 20 25 25 24 20 25 25 24 21 24 25 24 20 22 23 22 19
kW 1.85 1.89 1.95 2.02 2.00 2.04 2.11 2.18 2.13 2.18 2.25 2.33 2.24 2.30 2.37 2.46 2.34 2.40 2.48 2.57 2.43 2.48 2.57 2.66
Amps 7.9 8.1 8.3 8.6 8.5 8.7 9.0 9.3 9.2 9.4 9.7 10.1 9.8 10.0 10.3 10.7 10.4 10.6 11.0 11.4 11.0 11.2 11.6 12.0
Hi PR 225 242 255 266 252 271 287 299 287 309 326 340 327 352 371 387 368 396 418 436 406 437 462 481
Lo PR 110 117 128 137 117 124 135 144 121 129 141 150 127 135 148 158 133 142 155 165 138 147 160 171
850
MBh 27.6 28.1 29.4 31.4 26.9 27.4 28.7 30.7 26.3 26.8 28.0 29.9 25.6 26.1 27.4 29.2 24.3 24.8 26.0 27.7 22.6 23.0 24.1 25.7
S/T 0.88 0.85 0.76 0.62 0.91 0.88 0.79 0.64 0.93 0.90 0.81 0.66 0.96 0.93 0.84 0.68 1.00 0.96 0.87 0.71 1.00 0.97 0.88 0.71
∆T 26 26 24 21 26 26 25 21
27 26 25 21 27 26 25 21 26 26 24 21 24 24 23 20
kW 1.83 1.87 1.93 2.00 1.98 2.02 2.09 2.16 2.11 2.16 2.23 2.31 2.22 2.28 2.35 2.44 2.32 2.38 2.46 2.54 2.41 2.46 2.55 2.64
Amps 7.9 8.0
8.3 8.6 8.4 8.6 8.9 9.2 9.1 9.3 9.6 10.0 9.7 9.9 10.3 10.6 10.3 10.6 10.9 11.3 10.9 11.2 11.5 11.9
Hi PR 223 240 253 264 250 269 284 296 284 306 323 337 324 348 368 383 364 392 414 431 402 433 457 477
Lo PR 109 116 127 135 116 123 134 143 120 128 139 148 126 134 146 156 132 141 153 163 137 145 159 169
745
MBh 25.4 25.9 27.1 29.0 24.8 25.3 26.5 28.3 24.2 24.7 25.9 27.6 23.7 24.1 25.3 26.9 22.5 22.9 24.0 25.6 20.8 21.2 22.2 23.7
S/T 0.85 0.82 0.74 0.60 0.88 0.85 0.76 0.62 0.90 0.87 0.78 0.64 0.93 0.90 0.81 0.66 0.96 0.93 0.84 0.68 0.97 0.94 0.85 0.69
∆T 27 26 25 21 27 26 25 22 27 26 25 22 27 27 25 22 27 26 25 22 25 25 23 20
kW 1.78 1.82 1.88 1.95 1.93 1.97 2.04 2.11 2.05 2.10 2.17 2.25 2.17 2.22 2.29 2.37 2.26 2.31 2.39 2.48 2.34 2.40 2.48 2.57
Amps 7.7 7.8 8.1 8.3 8.2 8.4 8.7 9.0 8.9 9.1 9.4 9.7 9.5 9.7 10.0 10.3 10.0 10.3 10.6 11.0 10.6 10.9 11.2 11.6
Hi PR 216 232 245 256 242 261 275 287 276 297 313 327 314 338 357 372 353 380 401 418 390 420 443 462
Lo PR 106 113 123 131 112 119 130 139 116 124 135 144 122 130 142 151 128 136 149 159 133 141 154 164
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI (TVA) condions kW = Total system power
High & low pressures are measured at the liquid & sucon access ngs. Amps = outdoor unit amps (comp.+ fans)