- Goodman Mfg. Co. LP. Gas Heater User Manual

26
APPENDIX B ELECTRICAL DATA
NOTES: See unit nameplate for proper overcurrent protection.
MIN MAX Qty RLA LRA Qty HP RLA HP FLA
208/230-60-3 187 253 2 33.3 239.0 3 1/3 2.40 BD STD STATIC 5.0 12.7
460-60-3 414 506 2 17.9 125.0 3 1/3 1.20 BD STD STATIC 5.0 6.4
575-60-3 518 633 2 12.8 80.0 3 1/3 0.90 BD STD STATIC 5.0 5.1
20 TON
ELECTRICAL DATA
ID MOTOR
APPL
COMPRESSOR
(ea)
OD FAN MOTORS
(ea)
ID FAN
MOTOR
VOLTAGE
LIMITATIONS
VOLTAGE
(NAMEPLATE)
MODELS
MIN MAX Qty RLA LRA Qty RLA LRA Qty HP RLA HP FLA
208/230-60-3 187 253 1 29.5 195.0 1 25.0 164.0 3 1/3 2.40 BD STD STATIC 5.0 12.7
460-60-3 414 506 1 14.7 95.0 1 12.2 100.0 3 1/3 1.20 BD STD STATIC 5.0 6.4
575-60-3 518 633 1 12.2 80.0 1 9.0 78.0 3 1/3 0.90 BD STD STATIC 5.0 5.1
SMALLER
COMPRESS OR
15 TON
ELECTRICAL DATA
ID MOTOR
APPL
LARGER
COMPRESSOR
OD FAN MOTORS (ea) ID FAN MOTOR
VOLTAGE
LIMITATIONS
VOLTAGE
(NAMEPLATE)
MODELS