- Goodman Mfg. Co. LP. Gas Heater User Manual
25
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - HIGH STATIC
NOTES:
High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow tables represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.0
--- --- --- --- --- --- --- --- 6690 3.69 6008 3.02 5321 2.43
1.2
--- --- --- --- --- --- 6653 3.95 5922 3.22 5182 2.58 --- ---
1.4
--- --- --- --- 6634 2.80 5857 3.44 5056 2.74 --- --- --- ---
1.6
--- --- 6638 4.5
5
5808 2.43 4948 2.91 --- --- --- --- --- ---
1.8
6683 4.93 5784 3.95 4855 2.05 --- --- --- --- --- --- --- ---
2.0 5803 4.27 4788 3.32 --- --- --- --- --- --- --- --- --- ---
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.0
--- --- --- --- --- ---
9001 6.83 8394 6.01 7797 4.78 7227 4.28
1.2
--- --- --- ---
8891 6.83 8262 6.15 7632 5.35 7012 4.20
--- ---
1.4
--- ---
8811 6.86 8148 6.15 7495 5.48 6841 4.71
------------
1.6
--- ---
8065 6.19 7377 5.48
--- --- --- --- --- --- --- ---
1.8 7998 6.89 7290 5.52
--- --- --- --- --- --- --- --- --- ---
2.0 7221 6.10 --- --- --- --- --- --- --- --- --- --- --- ---
ESP, In H
2
O
TURNS OPEN
0123456
CPG240 HIGH STATIC BELT DRIVE
CPG180 HIGH STATIC BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0123456