APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD HORIZONTAL
NOTES:
High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow tables represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
--- --- --- --- --- --- --- 0.00 6827 2.67 6394 2.28 5982 1.94
0.4
--- --- --- --- 7079 3.20 6623 2.76 6161 2.34 5706 1.98 5271 1.66
0.6
--- --- 6903 3.32 6405 2.83 5923 2.41 5434 2.02 4949 1.68 --- ---
0.8
6717 3.42 6198 2.92 5668 2.45 5152 2.05 --- --- --- --- --- ---
1.0
5975 2.99 5418 2.51 --- --- --- --- --- --- --- --- --- ---
1.2 5147 2.55 --- --- --- --- --- --- --- --- --- --- --- ---
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 --- --- --- --- 9359 4.92 8991 3.79 8621 3.54 8188 3.27 7826 3.04
0.4 --- --- 9018 3.18 8632 4.39 8251 3.39 7867 3.15 7363 2.85 6992 2.63
0.6
--- --- 8279 2.96 7879 3.86 7484 2.99 7085 2.75 --- --- --- ---
0.8 7957 4.82 7513 2.73 7097 3.35 --- --- --- --- --- --- --- ---
1.0
7179 4.23 6716 2.49 --- --- --- --- --- --- --- --- --- ---
1.2 6368 3.66 --- --- --- --- --- --- --- --- --- --- --- ---
CPG180 STANDARD BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0123456
CPG240 STANDARD BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0123456