Solar Controller User Manual (GP-PWM-30-UL)

GP-PWM-30-UL
_______________________________________________________________________
7
© 2019 Go Power!
2.0 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR MODEL
GP-PWM-30-UL THAT SHOULD BE FOLLOWED DURING
INSTALLATION AND MAINTENANCE OF THE CHARGE
CONTROLLER.
Disconnect all
power sources
Electricity can be very dangerous. Installation
should be performed only by a licensed
electrician or qualified personnel.
Battery and wiring
safety
Observe all safety precautions of the battery
manufacturer when handling or working
around batteries. When charging, batteries
produce hydrogen gas, which is highly
explosive.
Wiring connections
Ensure all connections are tight and secure.
Loose connections may generate sparks and
heat. Be sure to check connections one week
after installation to ensure they are still tight.
Work safely
Wear protective eyewear and appropriate
clothing during installation. Use extreme
caution when working with electricity and
when handling and working around batteries.
Observe correct
polarity
Reverse polarity of the Battery 1 terminals will
cause the controller to give a warning tone.
Reverse connection of Battery 2 terminals will
not cause an alarm. However, the controller
will not charge or display information for
Battery 2 on the LCD. The controller will not
function unless Battery 1 terminals are
connected to a battery with proper polarity.
Failure to correct this fault could damage the
controller.
Do not exceed the
GP-PWM-30-UL
max current ratings
The maximum current of the solar system is
the sum of parallel-connected PV module
rated short circuit Currents (Isc) multiplied by
1.25. The resulting system current is not to
exceed 37.5A. If your solar system exceeds
this value, contact your dealer for a suitable
controller alternative.
Do not exceed the
GP-PWM-30-UL
max voltage ratings
The maximum voltage of the array is the sum
of the PV modulerated open-circuit voltage of
the series connected modules multiplied by
1.25 (or by a value from NEC 690.7 provided
in Table 690.7 A). The resulting voltage is not
to exceed 35V. If your solar system exceeds
this value, contact your dealer for a suitable
controller alternative.