3.4 AC WIRING
The cables linking the GP-SW1500TS to the appliances are the AC cables. The following
points must be observed for the AC Wiring
•
A branch rated over current protection at the time of installation shall be provided
by others for the AC output circuit.
• Depending on the usage scenario, the AC output of the inverter may require a
user installed breaker or fuse.
• For 20A branch circuit protection, additional breakers are needed for the GFCI
receptacles.
• Review the safety information at the start of this manual before completing any
AC wire installation steps.
•
All AC Wiring must be approved for the application (RV, Marine, Residential). For
RV applications, this may be solid wire in multi-conductor cables, but stranded
wire is required if single conductors are used.
• All wiring must be rated to 75°C or higher.
•
Do not connect the AC Output to an AC Power source (generator / shore power).
Severe damage may occur and will not be covered under the warranty.
• Always use properly rated circuit breakers / fuses. Make sure all cables have
a smooth bend radius and no kinks are present.
3.4.1 GP-SW1500TS AC WIRING TABLE
Terminal (F) Wire Colour Wire AWG Max Wire Length
AC
Output
Line (L) Black
100-120 VAC: #12 Up to 50ft
Neutral (N) White
AC
Input
Line (L) Brown
Neutral (N) Blue
Ground
Green / Yellow
or Bare Copper
#14 Up to 32ft
INSTALLATION