Datasheet

4
Network Power > Sprinter P / XP > Technical data
Sprinter P / XP
Technical data
Technical characteristics and data
Container, terminal and torque
11 Nm8 Nm6 Nm
> Container: - UL 94-HB = Polypropylene (PP)
- UL 94-V0 = Polypropylene (PP)
Figures are also valid for UL 94-V0 version.
Change »H« to »V« in the part number. E.g.:
> Standard: NAXP122500 H P0FA
> UL 94-V0: NAXP122500 V P0FA
P12V600, P12V875 and XP12V2500 with VdS approval.
NEW
Type
Part number
Nom.
voltage
V
Power
10 min
1.60 Vpc
25°C
W/block
Nominal
capacity
C
10
1.80
Vpc 25°C
Ah
Length
(l)
max. mm
Width
(b/w)
max. mm
Height
(h1)
max. mm
Height
incl. con-
nectors
(h2)
max. mm
Weight
approx.
kg
Internal
resist-
ance
mOhm
Short
cicuit
current
A
Terminal
P6V1700 NAPW061700HP0MC 6 2210 122 273 167 191 191 25.0 1.80 3416 M-M8
XP6V2800 NAXP062800HP0FA 6 2780 195 309 172 223 241 32.6 1.60 3828 F-M6
P12V600 NAPW120600HP0MA 12 791 24.0 169 128 175 175 9.50 15.4 824 M-M6
P12V875 NAPW120875HP0MC 12 1157 41.0 200 169 176 176 14.5 10.6 1178 M-M6
XP12V1800 NAXP121800HP0FA 12 1840 56.4 220 172 219 235 22.5 8.10 1558 F-M6
XP12V2500 NAXP122500HP0FA 12 2450 69.5 262 172 223 239 27.7 6.20 2046 F-M6
XP12V3000 NAXP123000HP0FA 12 3040 92.8 309 172 223 239 32.8 5.20 2425 F-M6
XP12V3400 NAXP123400HP0FA 12 3400 105 351 172 223 239 36.0 4.50 2767 F-M6