Safety data sheet

Page 1 of 5
MATERIAL SAFETY DATA SHEET
I. PRODUCT IDENTIFICATION
MANUFACTURER CHEMICAL/TRADE NAME Maintenance Free Battery
Deutsche Exide GmbH (as used on label) Valve Regulated Battery
Thiergarten Sealed Lead-Acid Battery
63654 Budingen CHEMICAL FAMILY/ Electric Storage Battery
Germany CLASSIFICATION
DISTRIBUTED BY DATE ISSUED: February 1, 2008
Exide Technologies Page 1 of 5
13000 Deerfield Parkway, Bldg. 200
Alpharetta, Georgia 30004
FOR INFORMATION: Primary: MACTEC Engineering and
FOR EMERGENCY Consulting, Inc.
CHEMTREC (800) 424-9300 Attn: Juliann Cothran (770) 421-3485
CHEMTREC INTERNATIONAL (703) 527-3887 – Collect Secondary:
24-hour Emergency Response Contact Attn: Eric Murray (800) 523-4622
Ask for Environmental Coordinator Attn: Fred Ganster (610) 921-4052
II. HAZARDOUS INGREDIENTS/IDENTITY INFORMATION
Approximate Air Exposure Limits (µg/m
3
)
Components CAS Number % by Wt. OSHA ACGIH NIOSH
Inorganic compounds of:
Lead
Tin
Calcium
7439-92-1
7440-31-5
7440-70-2
60-68
0.28
0.03
50
2000
-
50
2000
-
50
2000
-
Electrolyte (hydrogel):
Sulfuric Acid (Diluted sulfuric acid in
solid state, percentage acid: 38.5%)
Silicon Dioxide
7664-93-9
60676-86-0
17-22
4-6
1000
N/A
200
N/A
1000
N/A
Case Material:
Acrylonitrile Butadiene Styrene or
Polypropylene
9003-56-9
9003-07-0
4-12
N/A
N/A
N/A
N/A
N/A
N/A
NOTE: Inorganic lead and electrolyte (water and sulfuric acid solution) are the primary components of every battery manufactured by
Exide Technologies or its subsidiaries. Other ingredients may be present dependent upon battery type. Polypropylene is the principal case
material of automotive and commercial batteries.
III. PHYSICAL DATA - ELECTROLYTE
Boiling Point
112°C
Density
1.30 g/cm
3
Point of Solidification
-69°C
Solubility in Water
100%
Vapor Pressure
(mm Hg) 77° F
21 mbar
Evaporation Rate
(Butyl acetate=1)
Less Than 1
Vapor Density (AIR=1)
Greater than 1
Appearance and Odor
A white translucent gel; no
apparent odor. A battery is a
manufactured article.
% Volatiles by Weight
Not Applicable
IV. FIRE AND EXPLOSION HAZARD DATA
Flash Point: Not Applicable
Flammable Limits: LEL = 4.1% (Hydrogen Gas in air) ; UEL = 74.2%
Extinguishing media: CO
2
; foam; dry chemical
Special Fire Fighting Procedures:
Use positive pressure, self-contained breathing apparatus. Beware of acid splatter during water application and wear acid-