12.8.3 Heating circuit adjustment
1
2
3
4
Key
1 Speed control
2 Speed III (factory setting)
3 Speed II
4 Speed I (not applicable to this system)
Turn the control (1) to select pump speed II or III, in
accordance with the ow / pressure curve below.
Hydraulic module pump ow / pressure curve
60
50
40
30
20
10
0
300 600 900 1200
B
21
Key
1 Speed 2
2 Speed 3
A Available pressure (kPa)
B Flow within the circuit (l/h)
12.8.4 Venting the HP circuit
The venting of the HP circuit allows you to purge any air in the
HP circuit.
Ø14
A
B
1
3
4
1
2
Key
1 Air trap
2 Ø14mmatwrench(*)
3 Hose
4 Container (*)
(*) Not included
Connect one end of the hose (3) to the trap (1).
Insert the other end of the hose (3) into the container (4) in
order to recover any residual glycol during the venting of the
circuit.
Using the buttons ,
select Vent HP circuit on the screen.
Press the button
to conrm.
Conrm with the button in
order to begin the venting process.
You can start the heating circuit bleed at
the same time.