INSTALLATION
6.1.1 Access to main board
B
A
2
1
Key
1 Handle
2 Box
Remove the box (2) by pulling it toward you using the handle
(1).
6.2 Electrical wiring
e
Insert the Ebus 24V cable and 230V power cable
in different casings.
B
A
5
4
3
2
1
6
Key
1 230 V supply connection terminal block
2 Ebus connection terminal
3 Clamp for Ebus cable
4 Clamp for 230 V power cable
5 Access hatch to electrical connections
6 Access hatch screw
Remove the screw (6) from the access hatch (5).
Open the access hatch (5).
Ebus Connection
Connect a 2 x 0.75 mm ² cable to the heat pump’s BUS
terminal (2).
Pass the cable through the cable clamp (3).
Connect the Ebus cable to the Systempro control unit.
Tighten the clamp.
230V Connection
Connect a 3 x 2.5 mm ² cable to the heat pump’s power
terminal 230V (1).
Pass the cable through the cable clamp (4).
Connect the heat pump’s power cable to the installation’s
electrical panel: single-phase network 230V + neutral + earth.
Close the access hatch with the screw (6).
Tighten the clamp.
6.3 Hydraulic module
NTC1REL1
A
A
B
1
2
1
3
4
3
Key
1 Pump cable
2 Pump cable clamp
3 Flow heating temperature sensor cable
4 Flow heating temperature sensor cable clamp
Component Voltage (cable section)
Pump 230 V (3 x 0.75 mm²)
Temperature sensor 3.3 V (2 x 0.34 mm²)
Pass the pump cable (1) through the cable clamp (2).
Connect the cable (1) to the REL1 terminal in the Systempro
control.
Tighten the clamp (2).
Pass the temperature sensor cable (3) through the clamp (4).
Connect the cable (3) to the NTC1 terminal in the
Systempro control.
Tighten the clamp (4).