INSTALLATION
Commissioning
• Open all the hydraulic circuits’ valves.
7 Filling the glycol circuit
b
Warning! Do not dispose of glycol into drains
and the environment.
b
We recommend that you use propylene glycol
enriched with corrosive inhibitors.
• Mix 1 part propylene glycol with 2 parts water. This
mixture ensures antifreeze protection down to an exterior
temperature of -15 °C.
• Use an antifreeze test kit to ensure accurate dosing.
Ø14
A
B
1
3
4
1
2
Key
1 Air trap
2 Ø14mmatwrench(*)
3 Hose
4 Deposit(*)
(*) Notincluded
• Connect one end of the hose (3) to the trap (1).
• Insert the other end of the hose (3) into the container (4) in
order to recover any residual brine during the lling of the
circuit.
• Using a at wrench (2), open the trap (1) a ¼ turn.
1
2
3
4
A
B
5
6
8
7
Key
1 Glycolcontainer(*)
2 Fillingpump(*)
3 Hoseleadingtothellingpumpoutput(*).
4 Cap
5 3-wayvalvewithshut-offvalveforlling
6 Manometer
7 3-wayvalvewithshut-offvalveforlling
8 Hoseleadingtothellingpumpreturn(*)
(*) Notsuppliedwiththeappliance
A Valveinllingmode
B Valve in normal operating mode
• In order to drain the glycol circuit after lling, use a ll pump
(2).
• Remove the caps (4) from the valves (5) and (7).
• Connect the lling pump hose (3) to the valve (5).
• Insert the hose (8) into the container and (1) and connect it
to the valve (7).
• Open valves (5) and (7) in (A) position as shown in the
illustration above.
• Start the ll pump (2) and ll the glycol circuit.
• Continue running the lling pump until completely purged of
air (8).
• Close the air trap located on the heat pump.
• Close the valve (7) in (B) position and ensure the glycol
circuit is left with a pressure of between 1.5 and 2 bars with
the aid of the manometer (6).
• Close the valve (5) in (B) position and stop the lling pump.