Manual

0020096317_01 - 08/10 - Glow-worm
- 11 -
INSTALLATION
5.1.3 Removal of condensate
When the heat pump is operational, it will produce condensation
that needs to be drained off.
1
2
3
A
1
3
2
B
Key
A Congurationwithinclinationtotheleft
B Congurationwithinclinationtotheright
1 Heat pump
2 Plug
3 Drainage elbow
Insert the drainage elbow (3) and pipe into the correct
opening depending on the angle of the heat pump.
Seal off the other opening with the supplied plug (2).
5.2 Boiler circuit
5.2.1 Connection from the hydraulic module to
the boiler
i
Make the connection limiting the load losses to a
minimum (the circuit should be as short as possible,
avoid bends and narrow sections...).
i
Refer to the installation manual delivered with the
boiler for domestic hot water system connections.
1
2
4
3
5
Key
1 Boiler
2 Return tubing leading to the boiler (not included))
3 Flow boiler tubing (not included)
4 Flow boiler connection (Ø ¾")
5 Return boiler connection (Ø ¾")
Connect a pipe (2) to the return connection (5) leading to the
boiler.
Connect a pipe (3) to the ow connection (4) leading away
from the boiler.
Refer to the boiler instructions to connect the pipes (2) and
(3) to the boiler.
5.2.2 Connection of the domestic hot water
cylinder (option)
Refer to the instructions supplied with the 2-way valve
and the domestic hot water cylinder for their hydraulic
connections to the boiler circuit.