Owner manual
- 27 -
i
At the time of commissioning, complete all relevant
sections of the Benchmark Checklist located on the
inside back pages of this document
•
•
•
•
•
b
Warning! Do not dispose of glycol into drains and the
environment.
b
We recommend that you use propylene glycol
enriched with corrosive inhibitors.
•
•
•
•
•
i
The level of glycol may decrease during the rst month
following the commissioning of the installation. It may
also vary in accordance with the outdoor temperature.
•
e
Make sure that all the electrical connections have
been made.
b
Make sure that the setting for the maximum temperature
at heating ow is compatible with the installation.
•
•
•
•
•
•
b
The maximum heating output temperature must be
adjusted in accordance with the characteristics of
your installation.
b
Ensure that the heating curve setting is compatible
with the installation.
b
Make sure that the functioning mode for the boiler's
circulator is not in permanent mode, but synchronised
with heating demand (with the room thermostat).
2
4
3
1
•
•
•
•
•
•