6 Boiler Location, Flue and Ventilation
Diagram 6.2
MINIMUM SITING DIMENSIONS FOR THE
POSITIONING OF FLUE TERMINALS MM
HORIZONTAL FLUES
A DIRECTLY BELOW, ABOVE OR
HORIZONTALLY TO AN OPENING, AIR BRICK,
OPENING WINDOWS, AIR VENT, OR ANY
OTHER VENTILATION OPENING 300
B BELOW GUTTER, DRAIN/SOIL PIPE 75
C BELOW EAVES 200
D BELOW A BALCONY OR CAR PORT 200
E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES 150
F FROM INTERNAL/EXTERNAL CORNERS
OR TO A BOUNDARY ALONGSIDE THE
TERMINAL 300
G ABOVE ADJACENT GROUND OR
BALCONY LEVEL 300
H FROM SURFACE OR A BOUNDARY
FACING THE TERMINAL 600
I FACING TERMINALS 1200
J FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING 1200
K VERTICAL FROM A TERMINAL 1500
L HORIZONTALLY FROM A TERMINAL 300
VERTICAL FLUES
M FROM ADJACENT WALL TO FLUE 300
N FROM ANOTHER TERMINAL 600
P FROM ADJACENT OPENING WINDOW 1000
Q ABOVE ROOF LEVEL 300
11508
Diagram 6.3
6.2 Terminal guard, see diagram 6.3.
A terminal guard is required if persons could come into contact
with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide
a minimum of 50mm clearance from any part of the terminal and
to be central over the terminal.
A suitable terminal guard type K3 can be supplied by:
Tower flue components Ltd.
Morley road
Tonbridge
Kent
TN9 1RA
6.3 Flue options
There are various flue systems to choose from as follows:
Horizontal telescopic rear flue pack.
Horizontal telescopic top flue pack.
Horizontal top flue pack.
Horizontal extended flue pack.
Vertical flue pack.
Twin flue pack.
Extensions, 90° and 45° bends.
For detailed information refer to flue options guide. This is
available from your nearest stockist.
6.4 Cupboard or compartment ventilation
The boiler can be fitted in a cupboard or compartment without
the need for permanent ventilation.