Item Brochure

Gillette Generators, Inc.
2921 Thorne Dr. Elkhart, IN 46514 Ph: 574-264-9639 Fax: 574-262-1840 Web: www.gillettegenerators.com spc4-180810
2
GENERATOR SPECIFICATIONS
Manufacturer ................................... Stamford Electric Generators
Model & Type ............ UCI224F-06, 4 Pole, 4 Lead, Single Phase
....... UCI224F-311, 4 Pole, 12 Lead re-connectable, Three Phase
........................ UCI224F-17, 4 Pole, 6 Lead, 600V, Three Phase,
Exciter ..................................................... Brushless, shunt excited
Voltage Regulator ....................................... Solid State, HZ/Volts
Voltage Regulation ................................ ½%, No load to full load
Frequency ................................ Field convertible, 60 HZ to 50 HZ
Frequency Regulation ............. ½% (½ cycle, no load to full load)
Unbalanced Load Capability ..................... 100% of standby amps
Total Stator and Load Insulation ........................... Class H, 180°C
Temperature Rise ......... 130°C R/R, standby rating @ 40°C amb.
1 Ø Motor Starting @ 30% Voltage Dip (240V) ............ 168 kVA
3 Ø Motor Starting @ 30% Voltage Dip (208-240V) ..... 190 kVA
3 Ø Motor Starting @ 30% Voltage Dip (480V) ............ 260 kVA
3 Ø Motor Starting @ 30% Voltage Dip (600V) ............ 290 kVA
Bearing ..................................................... 1, Pre-lubed and sealed
Coupling .......................................................... Direct flexible disc
Total Harmonic Distortion ............... Max 3½% (MIL-STD705B)
Telephone Interference Factor ............ Max 50 (NEMA MG1-22)
Deviation Factor ................................. Max 5% (MIL-STD 405B)
Ltd. Warranty Period .............. 24 Months from date of start-up or
....................................................... 1000 hours use, first to occur.
ENGINE ___________________________________
Manufacturer ........................................................ General Motors
Model and Type .............. Ind. Power Train, Vortec, 5.7L, 4 cycle
Aspiration .......................................................................... Natural
Cylinder Arrangement ......................................... 8 Cylinders, V-8
Displacement Cu. In. (Liters) .......................................... 350 (5.7)
Bore & Stroke In. (Cm.) .............................. 4 x 3.48 (10.2 x 8.84)
Compression Ratio ................................................................ 9.1:1
Main Bearings & Style ................................ 5M 400 Copper Lead
Cylinder Head ................................................................. Cast Iron
Pistons .................................................... High, Silicon Aluminum
Crankshaft ................................................................. Nodular Iron
Exhaust Valve ........................................................... Forged Steel
Governor ....................................................................... Electronic
Frequency Reg. (no load-full load) ............................ Isochronous
Frequency Reg. (steady state) ............................................ ± 1/4%
Air Cleaner ......................................... Dry, Replaceable Cartridge
Engine Speed ................................................ ................ 1800 rpm
Piston Speed, ft/min (m./min) ....................... .............. 1044 (318)
Max Power, bhp (kwm) Standby /LPG ......... ................. 108 (81)
Max Power, bhp (kwm) Standby/NG ............ ................. 100 (75)
Ltd. Warranty Period .......... 12 Months or 2000 hrs., first to occur
FUEL SYSTEM ____________________________
Type ................................ LPG or NAT. GAS, Vapor Withdrawal
Fuel Pressure (kpa), in. H
2
O* ......................... (1.74-2.74), 7”-11”
Secondary Fuel Regulator ................... NG or LPG Vapor System
Auto Fuel Lock-Off Solenoid ........................ Standard on all sets
Fuel Supply Inlet Line ..................................................... 1” NPTF
* Measured at gen-set fuel inlet, downstream of any dry fuel
accessories.
GENERATOR FEATURES
World Renown Stamford Electric Generator having UL-1446
certification.
Full generator protection with Deep Sea 7420 controller,
having UL-508 certification.
Automatic voltage regulator with over-excitation, under-
frequency compensation, under-speed protection, and EMI
filtering. Entire solid-state board is encapsulated for
moisture protection.
Generator power ratings are based on temperature rise,
measured by resistance method, as defined in MIL-STD
705C and IEEE STD 115, Method 6.4.4.
Power ratings will not exceed temperature rise limitation for
class H insulation as per NEMA MG1-22.40.
Insulation resistance to ground, exceeds 1.5 meg-ohm.
Stator receives 2000 V. hi-potential test on main windings,
and rotor windings receive a 1500 V. hi-potential test, as per
MIL-STD 705B.
Full amortisseur windings with UL-1446 certification.
Complete engine-generator torsional acceptance, confirmed
during initial prototype testing.
Full load testing on all engine-generator sets, before shipping.
Self ventilating and drip-proof & revolving field design
FUEL CONSUMPTION
LP GAS: FT
3
/HR (M
3
/HR) STANDBY
100% LOAD 330 (9.3)
75% LOAD 240 (7.0)
50% LOAD 195 (5.5)
LPG = 2500 BTU X FT
3
/HR = Total BTU/HR
LPG Conversion: 8.50 FT
3
= 1 LB. : 36.4 FT
3
= 1 GAL.
NAT. GAS: FT
3
/HR (M
3
/HR) STANDBY
100% LOAD 800 (22.6)
75% LOAD 695 (20.0)
50% LOAD 500 (14.2)
NG = 1000 BTU X FT
3
/HR = Total BTU/HR
OIL SYSTEM
Type ......................................................................... Full Pressure
Oil Pan Capacity qt. (L) ...................................................5.0 (4.7)
Oil Pan Cap. W/ filter qt. (L) ...........................................6.5 (6.2)
Oil Filter .................................................. 1, Replaceable Spin-On
ELECTRICAL SYSTEM _____________________
Ignition System ............................................................. Electronic
Eng. Alternator and Starter:
Ground ..................................................................... Negative
Volts DC ............................................................................ 12
Max. Amp Output of Alternator ......................................... 70
Recommended Battery to -18°C (0°F): .. 12 VDC, Size BCI# 24F
Max Dimensions: .. 10 3/4" lg X 6 3/4” wi X 9" hi, with standard
round posts. Min. output at 600 CCA. Battery tray (max. dim.
at 12”lg x 7”wi), hold down straps, battery cables, and battery
charger, is furnished. Installation of (1) starting battery is
required, with possible higher AMP/HR rating, as described
above, if normal environment averages -13°F (-25°C) or cooler.
APPLICATION AND ENGINEERING DATA FOR MODEL SP-620-60 HZ
ENGINE SPECIFICATIONS AND APPLICATIONS DATA