60 HZ MODEL
SP-410
All generator sets are USA prototype built and thoroughly tested.
Production models are USA factory built and 100% load tested.
UL2200, UL1446, UL508, UL142, UL498
NFPA 110, 99, 70, 37
All generator sets meet NFPA-110 Level 1, when equipped with the
necessary accessories and installed per NFPA standards.
NEC 700, 701, 702, 708
NEMA ICS10, MG1, ICS6, AB1
ANSI C62.41, 27, 59, 32, 480, 40Q, 81U, 360-05
ASCE 7-05 & 7-10
All generator sets meet 180 MPH rating.
40CFR Part 60, 1048, 1054, 1065, 1068
RATINGS: All single phase gen-sets are dedicated 4 lead wiring, rated at unity (1.0) power factor. All three phase gen-sets are 12 lead wiring, rated at .8 power factor.
120°C “STANDBY RATINGS” are strictly for gen-sets that are used for back-up emergency power to a failed normal utility power source. This standby rating allows
varying loads, with no overload capability, for the entire duration of utility power outage. All gen-set power ratings are based on temperature rise measured by resistance
method as defined by MIL-STD 705C and IEEE STD 115, METHOD 6.4.4. All generators have class H (180°C) insulation system on both rotor and stator windings. All
factory tests and KW/KVA charts shown above are based on 120°C (standby) R/R winding temperature, within a maximum 40°C ambient condition. Generators operated at
standby power ratings must not exceed the temperature rise limitation for class H insulation system, as specified in NEMA MG1-22.40. Specifications & ratings are subject
to change without prior notice.
LIQUID COOLED LPG/NG ENGINE GENERATOR SET
GENERATOR RATINGS
LIQUID PROPANE GAS FUEL NATURAL GAS FUEL
GENERATOR MODEL
VOLTAGE
PH HZ
120
ºC
RISE STANDBY RATING
120
ºC
RISE STANDBY RATING
L-N L-L KW/KVA AMP KW/KVA AMP
SP-410-1-1
120 240 1 60 41/41 171 40/40 167
SP-410-3-2
120 208 3 60 40/50 139 40/50 139
SP-410-3-3
120 240 3 60 40/50 120 40/50 120
SP-410-3-4
277 480 3 60 40/50 60 40/50 60
SP-410-3-5
127 220 3 60 40/50 131 40/50 131
SP-410-3-16
346 600 3 60 40/50 48 40/50 48
Model
STANDBY
120ºC RISE
HZ LPG N.G.
SP
-
410
-
60 HERTZ
60 41 40
“OPEN” GEN-SET
There is no enclosure, so gen-set must be
placed within a weather protected area,
un-inhabited by humans or animals, with
proper ventilation. Silencer not supplied,
as installation requirements are not
known. However, this item is available as
optional equipment.
“LEVEL 2” HOUSED GEN-SET
Full aluminum weather protection and
superior sound attenuation for specific low
noise applications. Critical grade muffler is
standard.