Item Brochure
Gillette Generators, Inc. •
••
• 2921 Thorne Dr. Elkhart, IN • 46514 • Ph: 574-264-9639 • Fax: 574-262-1840 • Web: www.gillettegenerators.com • spc4-180810
2
GENERATOR SPECIFICATIONS
Manufacturer ................................... Stamford Electric Generators
Model & Type ............. 20L2U1706, 4 Pole, 4 Lead, Single Phase
.......... S1L2J1311, 4 Pole, 12 Lead re-connectable, Three Phase
................................ P14E17, 4 Pole, 6 Lead, 600V, Three Phase
Exciter ..................................................... Brushless, shunt excited
Voltage Regulator ....................................... Solid State, HZ/Volts
Voltage Regulation ................................ ½%, No load to full load
Frequency ................................ Field convertible, 60 HZ to 50 HZ
Frequency Regulation ............. ½% (½ cycle, no load to full load)
Unbalanced Load Capability ..................... 100% of standby amps
Total Stator and Load Insulation ........................... Class H, 180°C
Temperature Rise ......... 120°C R/R, standby rating @ 40°C amb.
1 Ø Motor Starting @ 30% Voltage Dip (240v) ............... 34 kVA
3 Ø Motor Starting @ 30% Voltage Dip (208-240V) ....... 41 kVA
3 Ø Motor Starting @ 30% Voltage Dip (480V) .............. 61 kVA
3 Ø Motor Starting @ 30% Voltage Dip (600V) .............. 72 kVA
Bearing ..................................................... 1, Pre-lubed and sealed
Coupling ......................................................... Direct flexible disc.
Total Harmonic Distortion ............... Max 3½% (MIL-STD705B)
Telephone Interference Factor ............ Max 50 (NEMA MG1-22)
Deviation Factor ................................. Max 5% (MIL-STD 405B)
Ltd. Warranty Period .............. 24 Months from date of start-up or
....................................................... 1000 hours use, first to occur.
ENGINE ___________________________________
Manufacturer ........................ PSI (Power Solutions International)
Model and Type ........................................................2.4L, 4 cycle
Aspiration .......................................................................... Natural
Cylinder Arrangement ................................... 4 Cylinders, In-Line
Displacement Cu. In. (Liters) ....................................... 143.5 (2.4)
Bore & Stroke In. (Cm.) ........................... 3.4 x 3.93 (8.65 x 10.0)
Compression Ratio ................................................................ 9.5:1
Main Bearings & Style ................................................... 4, Babbitt
Cylinder Head ................................................................. Cast Iron
Pistons .......................................................... 4, Silicon Aluminum
Crankshaft ................................................................. Nodular Iron
Exhaust Valve ........................................................... Forged Steel
Governor ....................................................................... Electronic
Frequency Reg. (no load-full load) ............................ Isochronous
Frequency Reg. (steady state) ............................................ ± 1/4%
Air Cleaner ......................................... Dry, Replaceable Cartridge
Engine Speed…………………………………………1800 rpm
Piston Speed, ft/min (m./min) ………………………..1080 (329)
Max Power, bhp (kwm) Standby/LPG .......... .................. 46 (34)
Max Power, bhp (kwm) Standby/NG ............ .................. 42 (31)
Ltd. Warranty Period ....... 12 Months or 2000 hrs., first to occur
FUEL SYSTEM ____________________________
Type ................................ LPG or NAT. GAS, Vapor Withdrawal
Fuel Pressure (kpa), in. H
2
O* ......................... (1.74-2.74), 7”-11”
Secondary Fuel Regulator ................... NG or LPG Vapor System
Auto Fuel Lock-Off Solenoid ........................ Standard on all sets
Fuel Supply Inlet Line ..................................................... 1” NPTF
* Measured at gen-set fuel inlet, downstream of any dry fuel accessories.
GENERATOR FEATURES
• World Renown Stamford Electric Generator having UL-1446
certification.
• Full generator protection with Deep Sea 7420 controller,
having UL-508 certification.
• Automatic voltage regulator with over-excitation, under-
frequency compensation, under-speed protection, and EMI
filtering. Entire solid-state board is encapsulated for
moisture protection.
• Generator power ratings are based on temperature rise,
measured by resistance method, as defined in MIL-STD
705C and IEEE STD 115, Method 6.4.4.
• Power ratings will not exceed temperature rise limitation for
class H insulation as per NEMA MG1-22.40.
• Insulation resistance to ground, exceeds 1.5 meg-ohm.
• Stator receives 2000 V. hi-potential test on main windings,
and rotor windings receive a 1500 V. hi-potential test, as per
MIL-STD 705B.
• Full amortisseur windings with UL-1446 certification.
• Complete engine-generator torsional acceptance, confirmed
during initial prototype testing.
•
Full load testing on all engine-generator sets, before shipping.
•
Self ventilating and drip-proof & revolving field design
FUEL CONSUMPTION
LP GAS: FT
3
/HR (M
3
/HR) STANDBY
100% LOAD 173 (4.9)
75% LOAD 139 (3.9)
50% LOAD 108 (3.0)
LPG = 2500 BTU X FT
3
= Total BTU/HR
LPG Conversion: 8.50 FT
3
= 1 LB. : 36.4 FT
3
= 1 GAL.
NAT. GAS: FT
3
/HR (M
3
/HR) STANDBY
100% LOAD 439 (12.4)
75% LOAD 342 (9.6)
50% LOAD 242 (6.8)
NG = 1000 BTU X FT
3
= Total BTU/HR
OIL SYSTEM
Type ......................................................................... Full Pressure
Oil Pan Capacity qt. (L) ...................................................4.5 (4.2)
Oil Pan Cap. W/ filter qt. (L) ..............................................5 (4.7)
Oil Filter .................................................. 1, Replaceable Spin-On
ELECTRICAL SYSTEM _____________________
Ignition System ............................................................. Electronic
Eng. Alternator and Starter:
Ground ..................................................................... Negative
Volts DC ............................................................................ 12
Max. Amp Output of Alternator ......................................... 70
Recommended Battery to -18°C (0°F): .. 12 VDC, Size BCI# 24F
Max Dimensions: .. 10 3/4" lg X 6 3/4” wi X 9" hi, with standard
round posts. Min. output at 600 CCA. Battery tray (max. dim.
at 12”lg x 7”wi), hold down straps, battery cables, and battery
charger, is furnished. Installation of (1) starting battery is
required, with possible higher AMP/HR rating, as described
above, if normal environment averages -13°F (-25°C) or cooler.
APPLICATION AND ENGINEERING DATA FOR MODEL SP-250-60 HZ
ENGINE SPECIFICATIONS AND APPLICATIONS DATA