Spec Sheet
Gillette Generators, Inc. •
••
• 2921 Thorne Dr. •Elkhart, IN • 46514 • Ph: 574-264-9639 • Fax: 574-262-1840 • Web: www.gillettegenerators.com • spc4-190104 
2
GENERATOR SPECIFICATIONS 
Manufacturer ................................... Stamford Electric Generators 
Model & Type ........... UCI274E-06, 4 Pole, 4 Lead, Single Phase 
 ............................... UCI274E-311, 4 Pole, 12 Lead, Three Phase 
 ....................... UCI274E-17, 4 Pole, 12 Lead, 600V, Three Phase 
Exciter ..................................................... Brushless, shunt excited 
Voltage Regulator ....................................... Solid State, HZ/Volts 
Voltage Regulation ................................ ½%, No load to full load 
Frequency ................................ Field convertible, 60 HZ to 50 HZ 
Frequency Regulation ............. ½% (½ cycle, no load to full load) 
Unbalanced Load Capability ........................ 100% of prime amps 
Total Stator and Load Insulation ........................... Class H, 180°C 
Temperature Rise .............105°C R/R, prime rating @ 40°C amb. 
1 Ø Motor Starting @ 30% Voltage Dip (240V) ............ 450 kVA 
3 Ø Motor Starting @ 30% Voltage Dip (208-240V) ..... 450 kVA 
3 Ø Motor Starting @ 30% Voltage Dip (480V) ............ 580 kVA 
Bearing ..................................................... 1, Pre-lubed and sealed 
Coupling .......................................................... Direct flexible disc 
Total Harmonic Distortion ............... Max 3½% (MIL-STD705B) 
Telephone Interference Factor ............ Max 50 (NEMA MG1-22) 
Deviation Factor ................................. Max 5% (MIL-STD 405B) 
Ltd. Warranty Period .............. 24 Months from date of start-up or 
 ....................................................... 1000 hours use, first to occur. 
ENGINE ___________________________________ 
Manufacturer ....................................... Power Solutions Inc. (PSI) 
Model and Type ......................... Heavy Duty 8.1LTCAC, 4 cycle 
Aspiration ............................. Turbocharged & Charge Air Cooled 
Cylinder Arrangement ...................................... 6 Cylinders, Inline 
Displacement Cu. In. (Liters) .......................................... 492 (8.1) 
Bore & Stroke In. (Cm.) ........................... 4.37 x 5.9 (11.1 x 13.9) 
Compression Ratio .............................................................. 10.5:1 
Main Bearings & Style .............................. 7, Precision Half-Shell 
Cylinder Head ................................................................. Cast Iron 
Pistons .................................................................. Cast Aluminum 
Crankshaft ................................................................. Forged Steel 
Exhaust Valve .........................................................Inconel, A193 
Governor ....................................................................... Electronic 
Frequency Reg. (no load-full load) ............................ Isochronous 
Frequency Reg. (steady state) ............................................ ± 1/4% 
Air Cleaner ......................................... Dry, Replaceable Cartridge 
Engine Speed ................................................  ....................... 1800 
Piston Speed, ft/min (m./min) .......................  .............. 1641 (500) 
Max Power, bhp (kwm) Prime/NG ...............  ................ 199 (149) 
Ltd. Warranty Period .......... 12 Months or 2000 hrs., first to occur 
FUEL SYSTEM  ____________________________ 
Type .............................................NAT. GAS, Vapor Withdrawal 
Fuel Pressure (kpa), in. H
2
O .......................................... (1.74), 7” 
Secondary Fuel Regulator ................................ NG Vapor System 
Auto Fuel Lock-Off Solenoid ........................ Standard on all sets 
Fuel Supply Inlet Line ..................................................... 2” NPTF
GENERATOR FEATURES 
•  World Renown Stamford Electric Generator having UL-1446 
certification. 
•  Full  generator  protection  with  Deep  Sea  7420  controller, 
having UL-508 certification. 
•  Automatic  voltage  regulator  with  over-excitation,  under-
frequency  compensation,  under-speed  protection,  and  EMI 
filtering.    Entire  solid-state  board  is  encapsulated  for 
moisture protection. 
•  Generator  power  ratings  are  based  on  temperature  rise, 
measured  by  resistance  method,  as  defined  in  MIL-STD 
705C and IEEE STD 115, Method 6.4.4. 
•  Power  ratings  will  not  exceed  temperature  rise  limitation  for 
class H insulation as per NEMA MG1-22.40. 
•  Insulation resistance to ground, exceeds 1.5 meg-ohm. 
•  Stator  receives  2000  V.  hi-potential  test  on  main  windings, 
and rotor windings receive a 1500 V. hi-potential test, as per 
MIL-STD 705B. 
•  Full amortisseur windings with UL-1446 certification. 
•  Complete  engine-generator  torsional  acceptance,  confirmed 
during initial prototype testing. 
• 
Full load testing on all engine-generator sets, before shipping.
• 
Self ventilating and drip-proof & revolving field design
FUEL CONSUMPTION 
NAT. GAS: FT
3
/HR (M
3
/HR)  PRIME 
100% LOAD  1330 (37.6) 
75% LOAD  1030 (29.1) 
50% LOAD  730 (20.6) 
NG = 1000 BTU X FT
3
/HR = Total BTU/HR
OIL SYSTEM   
Type ......................................................................... Full Pressure 
Oil Pan Capacity qt. (L) ............................................... 26.4 (25.0) 
Oil Pan Cap. W/ filter qt. (L) ....................................... 28.8 (27.0) 
Oil Filter .................................................. 1, Replaceable Spin-On 
ELECTRICAL SYSTEM _____________________ 
Ignition System ............................................................. Electronic 
Eng. Alternator/Starter: 24 VDC, negative ground, 45 amp/hr. 
Recommended battery to -18°C (0° F): .... (2) 12 VDC, BCI# 27, 
Max. Dimensions: 12”lg x 6 3/4” wi x 9” hi, with standard round 
posts. Min output 700 CCA.  Battery tray (max. dim. at 12”lg x 
7”wi).    This  model  has  (2)  battery  trays,  (2)  hold  down  straps, 
(2) sets of battery cables, and (1) battery charger.  Installation of 
(2)  12VDC  starting  batteries  connected  in  series  for  24VDC 
output  is  required,  with  possible  higher  AMP/HR  rating,  as 
described  above,  if  the  normal  environment  temperature 
averages -13° F (-25°C) or cooler. 
APPLICATION AND ENGINEERING DATA FOR MODEL PR-1000-60 HZ 