Instruction Manual

PAGE 27
MOUNTING DIMENSIONS FOR 3600 RPM SPP SERIES STANDBY SETS 18 KW
EXHAUST AIR
FROM RADIATOR
AND MUFFLER
MOUNTING PAD SHOULD
BE SET ON A 3" HIGH
BED OF CRUSHED GRAVEL
33" WI X 48" LG X 2" HI
OPTIONAL RE−INFORCED POLYETHYLENE
PAD. NOTE: PAD AND MOUNTING
HARDWARE IS SHIPPED LOOSE FOR
INSTALLATION BY OTHERS.
(2) MOUNTING HOLES
1/2" HIGH PITCH IN ROOF
FOR DRAINAGE OF WATER
COOLING AIR
INTO GENERATOR
DRY FUEL CONNECTION
INSTALLATION INSTRUCTIONS FOR INSTALLED GEN−SET
BASE TO FREE STANDING POLYBASE:
INSTALL (2) BOLTS THRU HOLES IN POLY BASE, AS SHOWN,
USING 7/16−18 HEX NUT TO LOCK BOLT IN PLACE. INSTALL
GEN−SET AND METAL BASE ONTO EXTENEDED 7/16−18 BOLT
AND SECURE WITH LARGE FLAT WASHER AND HEX NUT.
CAUTION: TIGHTEN NUT ONLY TO HOLD THE METAL BASE TO
PLY BASE. CONTINUED TIGHTENING WILL CAUSE METAL
BASE TO BEND INWARD.
NOTE: IF POLY BASE IN NOT USED, AND CEMENT PAD IS
REQUIRED, THE 2−BOLTS IN CEMENT PAD MUST BE 7/16−18
AND EXITED OUT FROM CEMENT, 3−1/2". USE CEMENT PAD
BOLT PLACEMENT DRAWING FOR POSITIONING THESE (2)
BOLTS.
NOTE: NOUNTING BOLTS ARE POSITIONED INSIDE LOCKED
CABINET, AS A DETERRENT TO THEFT. OUTSIDE MOUNTING
BOLTS HAVE MADE THEFT TOO EASY WHEN GAS AND
ELECTRIC LINES ARE REMOVED.
(2) 7/16−18 X 3−1/2" LG HHCS
5/16−18 HEX FLANGE NUT
AND FLAT WASHER
5/16−18 HEX FLANGE NUT
CEMENT PAD
ENGINE END
PANELS REMOVED
FOR MOUNTING
BOLT VIEW