PROGRAMMING THE CLOSED LIMIT: PULLTOOPEN
This is the most common installation. The CLOSED limit is when the operator is extended and the gate is in the closed position.
IMPORTANT
ONLY THE OPERATOR ARMS’ EXTENDED LIMIT IS ADJUSTABLE AND CAN BE SET WITH THE CONTROL
BOARD. THE ARMS’ RETRACTED POSITION IS FIXED AND IS NOT ELECTRONICALLY ADJUSTABLE.
THE OPEN POSITION IS SET BY HARDWARE MOUNTING ONLY. Please refer to the hardware installation to
make sure the retracted position is properly set/installed.
Installation Type Retracted Position Extended Position
Pull-To-Open Gate at the fully OPEN position (not
electronically adjustable)
Gate at the CLOSED position (elec-
tronically adjustable)
TURN THE CONTROL BOX ON
SETTING THE CLOSED LIMIT ON SINGLE GATES
A. Locate the 1st SET limit settings on the control board and press and
hold the JOG CLOSE button for the gate until the gate reaches the
desired closed position. The gate can move only if pressure is
maintained. Releasing the JOG button will stop the gate
immediately.
B. Both JOG OPEN or JOG CLOSE buttons are needed to ‘fine-tune’ your desired CLOSED position.
C. Press and hold the 1st set limit button on the control panel until it beeps, then release.
D. Press the transmitter button to activate the gates and let the gate open fully. You should hear a single beep.
When the gate reaches its OPEN position, the control board will sound a single beep, confirming the CLOSED limit
has been set.
E. Confirm the newly programmed CLOSED limit by pressing the remote transmitter button to activate the
gate and confirm the closed position has been set correctly. This limit is stored and remembered even if you
lose power.
F.
Repeat if needed to change your desired CLOSED position.
G. Test your system with the remote transmitter to make sure it opens and closes without errors.
1ST SET LIMIT SETTINGS