Instructions / Assembly
56
PREPARING
Ghost Controls 2017 | www.GhostControls.com
DIP SWITCH OPTION SETTINGS
There are four DIP Switches located on the main control board (shown)
that must be positioned properly for your particular installation.
DIP#1: OPEN DIRECTION
The opening direction of the gate operator is determined by DIP#1.
DIP Switch # OFF Position ON Position
1 Pull-To-Open (Factory
Default): Gate is pulled to open
into your property.
Push-To-Open Installation: Gate is pushed to open away from your
property.
DIP#2: ALARM WARNING
The warning alarm is determined by DIP#2.
DIP Switch # OFF Position ON Position
2 Warning Disabled:
AUTOCLOSE and initial gate
movement alarm warning is dis-
abled. This does not disable the
alarm warning for consecu-
tive obstruction as required by
UL325 safety standard.
Warning Enabled (Factory Default): AUTOCLOSE and initial gate
movement warning is enabled.
DIP#3: SAFETY (REVERSING) MODE
The mode of the safety setting for the system is determined by DIP#3.
DIP Switch # OFF Position ON Position
3 Patent-pending SafeForce®
Mode (Factory Default): Force
output is limited to ensure safe
operation as specified by Type
C in UL325 requirement.
Monitored Safety Mode: Monitored safety devices required /
Compatible GHOST CONTROLS
®
safety devices only. Monitored
safety devices must be present and operate properly as specified by
Type B1 or B2 in UL325 requirement. See monitored safety device
connection in the monitored photo eye instructions manual for
more details.